13.4 Utility Function (Fn) Operations on the Panel Operator
13.4.24 Software Reset (Fn030)
13-27
13
Panel Displays and Panel Operator Procedures
13.4.24
Software Reset (Fn030)
Refer to the following section for information on this utility function other than the procedure.
6.14 Software Reset on page 6-91
13.4.25
Polarity Detection (Fn080)
Refer to the following section for information on this utility function other than the procedure.
5.11 Polarity Detection on page 5-27
13.4.26
Tuning-less Level Setting (Fn200)
Refer to the following section for information on this utility function other than the procedure.
8.4 Tuning-less Function on page 8-11
Step
Panel Display after
Operation
Keys Operation
1
Press the MODE/SET Key to enter Utility Function
Mode.
2 Press the UP Key or DOWN Key to display Fn030.
3
Press the DATA/SHIFT Key for approximately one sec-
ond. The display shown at the left will appear.
4
Continue pressing the UP Key until the display shown
on the left appears.
Note: If you make a mistake during key operations, no_oP will
flash on the display for approximately one second.
5
Press the MODE/SET Key. The panel display will go
blank and then will change to the same initial status
display as when the power supply is turned ON.
MODE
/
SET
DATA
/
Step
Panel Display after
Operation
Keys Operation
1
Press the MODE/SET Key to enter Utility Function
Mode.
2 Press the UP Key or DOWN Key to display Fn080.
3
Press the DATA/SHIFT Key for approximately one sec-
ond. The display shown at the left will appear.
4 Press the MODE/SET Key to start polarity detection.
5 –
After polarity detection has been completed, the dis-
play shown on the left will appear.
The Servomotor will enter the servo OFF state.
6
Press the DATA/SHIFT Key for approximately one sec-
ond to return the display to Fn080.
MODE
SET
MODE
SET
Step
Panel Display after Oper-
ation
Keys Operation
1
Press the MODE/SET Key to enter Utility Function
Mode.