6.5 Speed Control
6.5.5 /V-CMP (Speed Coincidence Detection) Signal
6-25
Related Parameters
You set the speed at which to apply zero clamping as the zero clamping level (Pn501 or
Pn580). If you set a value that exceeds the maximum speed of the Servomotor, the actual
speed will be limited to the maximum speed of the Servomotor.
• Rotary Servomotors
• Linear Servomotors
6.5.5
/V-CMP (Speed Coincidence Detection) Signal
The /V-CMP (Speed Coincidence Output) signal is output when the Servomotor speed is the
same as the reference speed. This signal is used, for example, to interlock the SERVOPACK
and the host controller. You can use this output signal only during speed control.
The /V-CMP signal is described in the following table.
Note: You can use Pn50E = n.X (/V-CMP (Speed Coincidence Detection Output) Signal Allocation) to allocate
the /V-CMP signal to different output connector pins.
Refer to the following section for details on allocations.
6.1.2
Output Signal Allocations
on page 6-6
You can set the speed detection width for the /V-CMP signal in Pn503 (Speed Coincidence
Signal Detection Width) for a Rotary Servomotor or in Pn582 (Speed Coincidence Signal
Detection Width) for a Linear Servomotor.
• Rotary Servomotors
The signal is output when the difference between the reference speed and motor speed is
equal or less than the setting.
Pn501
Zero Clamping Level
Setting Range Setting Unit Default Setting When Enabled Classification
0 to 10,000
1 min
-1
10 Immediately Setup
Pn580
Zero Clamping Level
Setting Range Setting Unit Default Setting When Enabled Classification
0 to 10,000 1 mm/s 10 Immediately Setup
Typ e Signal Connector Pin No. Signal Status Meaning
Output /V-CMP
CN1-25 and CN1-26
(default setting)
ON (closed) The speed coincides.
OFF (open) The speed does not coincide.
Pn503
Speed Coincidence Signal Detection Width
Setting Range Setting Unit Default Setting When Enabled Classification
0 to 100
1 min
-1
10 Immediately Setup
If Pn503 is set to 100 and the speed reference is 2,000 min
-1
, the signal would be output
when the motor speed is between 1,900 and 2,100 min
-1
.
Pn503
Speed reference
The /V-CMP signal is output when the motor speed is in
the area between the dotted lines.
Motor speed