Parameter Details
12
12.10 n: Special Adjustment
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 1009
n1-05: Hunting Prevent Gain in Reverse
No.
(Hex.)
Name Description
Default
(Range)
n1-05
(0530)
Expert
Hunting Prevent Gain in
Reverse
Sets the performance of the hunting prevention function. This parameter adjusts Reverse run. Usually
it is not necessary to change this parameter.
0.00
(0.00 - 2.50)
Note:
When you set this parameter to 0, the value set in n1-02 [Hunting Prevention Gain Setting] is effective when the motor rotates in reverse.
Adjust this parameter in these conditions:
When n1-01 = 1, 2 [Hunting Prevention Selection = Enabled (Normal), Enabled (High Carrier Frequency)]: If
oscillation occurs when you operate a motor with a light load, increase the setting value in 0.1-unit increments.
When n1-01 = 1, 2, if the motor stalls: Decrease the setting value in 0.1-unit increments.
n1-08: Current Detection Method
No.
(Hex.)
Name Description
Default
(Range)
n1-08
(1105)
Expert
Current Detection Method
Sets how the drive decreases the motor vibration that is caused by leakage current. Usually it is not
necessary to change this parameter.
0
(0, 1)
0 : 2-Phases
1 : 3-Phases
Note:
Set this parameter to 1 to suppress motor vibrations caused by leakage current when the wiring distance is long.
n1-13: DC Bus Stabilization Control
No.
(Hex.)
Name Description
Default
(Range)
n1-13
(1B59)
Expert
DC Bus Stabilization
Control
Sets the oscillation suppression function for the DC bus voltage.
0
(0, 1)
0 : Disabled
1 : Enabled
Note:
If the DC bus voltage does not become stable with light loads and the drive detects ov [Overvoltage], set this parameter to 1.
n1-14: DC Bus Stabilization Time
No.
(Hex.)
Name Description
Default
(Range)
n1-14
(1B5A)
Expert
DC Bus Stabilization Time
Adjusts the responsiveness of the oscillation suppression function for the DC bus voltage. Set n1-13
= 1 [DC Bus Stabilization Control = Enabled] to enable this parameter.
100.0 ms
(50.0 - 500.0 ms)
Note:
Adjust this parameter in 100 ms increments.
n1-15: PWM Voltage Offset Calibration
No.
(Hex.)
Name Description
Default
(Range)
n1-15
(0BF8)
Expert
PWM Voltage Offset
Calibration
Sets the calibration method that the drive uses to decrease torque/current ripple.
Determined by A1-02
(0 - 2)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV