Parameter List
11
11.12 n: Special Adjustment
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 629
No.
(Hex.)
Name Description
Default
(Range)
Ref.
n7-11
(311B)
Expert
Drv Mode Switch
Hysteresis Band
Usually it is not necessary to change this setting. Sets the hysteresis level for Switching
Speed set in n7-10 [Pull-in Current Switching Speed].
When the speed is lower than n7-10 + n7-11 during acceleration, the drive enables pull-in
current.
Note:
• When the drive accelerates, it enables these settings:
–Motor speed ≤ n7-10 + n7-11: n8-51 [Pull-in Current @ Acceleration]
–Motor speed > n7-10 + n7-11: b8-01 [Energy Saving Control Selection]
• If there is a large quantity of oscillation when you operate in the low speed range,
increase the setting value.
• When it is most important to save energy in the low speed range, decrease the setting
value.
5.0%
(1.0 - 20.0%)
1023
n7-13
(311D)
Expert
Driving Method
Switching Time
Sets a time to enable the pull-in current commands.
If there is a large quantity of oscillation at speeds around n7-10 [Pull-in Current Switching
Speed], decrease the setting in 20 ms decrements.
100 ms
(0 - 1000 ms)
1023
n7-17
(3122)
Resistance
TemperatureCorrection
Sets the function to adjust for changes in the motor resistance value caused by changes in
the temperature.
0 : Invalid
1 : Valid (Only 1 time)
2 : Valid (Every time)
1
(0 to 2)
1023
◆ n8: PM Motor Control Tuning
No.
(Hex.)
Name Description
Default
(Range)
Ref.
n8-01
(0540)
Pole Position Detection
Current
Sets the Initial Rotor Position Estimated Current as a percentage where E5-03 [PM Motor
Rated Current (FLA)] = 100%. Usually it is not necessary to change this setting.
50%
(0 - 100%)
1024
n8-02
(0541)
Expert
Pole Alignment Current
Level
Sets the current at the time of polar attraction as a percentage where E5-03 [PM Motor
Rated Current (FLA)] = 100%. Usually it is not necessary to change this setting.
80%
(0 - 150%)
1024
n8-03
(0542)
Pole Position Detection
Time
Sets the length of the Current Starting Time, which is used for Z Pulse Offset Tuning.
Usually it is not necessary to change this setting.
1.5 s
(1.5 - 5.0 s)
1024
n8-04
(0543)
Expert
Pole Alignment Time
Sets the length of the Polar Attraction Time, which is used for Z Pulse Offset Tuning.
Usually it is not necessary to change this setting.
1.5 s
(1.5 - 5.0 s)
1024
n8-11
(054A)
Observer Calculation
Gain 2
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
Determined by n8-72
(0.0 - 1000.0)
1025
n8-14
(054D)
Expert
Polarity Compensation
Gain 3
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
1.000
(0.000 - 10.000)
1025
n8-15
(054E)
Expert
Polarity Compensation
Gain 4
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
0.500
(0.000 - 10.000)
1025
n8-21
(0554)
Expert
Motor Back-EMF (Ke)
Gain
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
0.90
(0.80 - 1.00)
1025
n8-23
(0556)
Expert
ACR q Gain @PoleEst
Sets the proportional gain for current regulator q-axis control when the drive estimates the
initial pole. Usually it is not necessary to change this setting.
0
(0 - 2000)
1025
n8-24
(0557)
Expert
ACR q Integral Time
@PoleEst
Sets the integral time for current regulator q-axis control when the drive estimates the
initial pole. Usually it is not necessary to change this setting.
0.0 ms
(0.0 - 100.0 ms)
1025
n8-25
(0558)
Expert
ACR q Limit @PoleEst
Sets the q-axis limit of the current regulator when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
0%
(0 - 150%)
1025