Parameter Details
12
12.10 n: Special Adjustment
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 1025
Sets the length of time that the pull-in current flows when the drive detects the motor magnetic pole of the rotors.
Note:
If the motor oscillates at the time of the polar attraction, increase the value in 0.5 s increments. If you set the value too high, the drive will
detect oL2 [Drive Overload].
■ n8-11: Observer Calculation Gain 2
No.
(Hex.)
Name Description
Default
(Range)
n8-11
(054A)
Observer Calculation Gain 2
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
Determined by n8-72
(0.0 - 1000.0)
Note:
When n8-72 = 0 [Speed Estimation Method Select = Method 1], the default value is 50.0. When n8-72 = 1 [Method 2], the default value is
150.0.
■ n8-14: Polarity Compensation Gain 3
No.
(Hex.)
Name Description
Default
(Range)
n8-14
(054D)
Expert
Polarity Compensation Gain
3
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
1.000
(0.000 - 10.000)
■ n8-15: Polarity Compensation Gain 4
No.
(Hex.)
Name Description
Default
(Range)
n8-15
(054E)
Expert
Polarity Compensation Gain
4
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
0.500
(0.000 - 10.000)
■ n8-21: Motor Back-EMF (Ke) Gain
No.
(Hex.)
Name Description
Default
(Range)
n8-21
(0554)
Expert
Motor Back-EMF (Ke) Gain
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
0.90
(0.80 - 1.00)
■ n8-23: ACR q Gain @PoleEst
No.
(Hex.)
Name Description
Default
(Range)
n8-23
(0556)
Expert
ACR q Gain @PoleEst
Sets the proportional gain for current regulator q-axis control when the drive estimates the initial
pole. Usually it is not necessary to change this setting.
0
(0 - 2000)
■ n8-24: ACR q Integral Time @PoleEst
No.
(Hex.)
Name Description
Default
(Range)
n8-24
(0557)
Expert
ACR q Integral Time
@PoleEst
Sets the integral time for current regulator q-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
0.0 ms
(0.0 - 100.0 ms)
■ n8-25: ACR q Limit @PoleEst
No.
(Hex.)
Name Description
Default
(Range)
n8-25
(0558)
Expert
ACR q Limit @PoleEst
Sets the q-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
0%
(0 - 150%)