EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.8 H: Terminal Functions
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 929
6A: Data Logger Error
Setting Value Function Description
6A Data Logger Error
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
90 to 93: DWEZ Digital Outputs 1 to 4
Setting Value Function Description
90 to 93 DWEZ Digital Outputs 1 to
4
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
A0 to A7: DWEZ Extended Digital Outputs 1 to 8
Setting Value Function Description
A0 to A7 DWEZ Extended Digital
Outputs 1 to 8
Sets the digital output for the DriveWorksEZ DO-A3 option card. Refer to the DriveWorksEZ online manual for more information.
100 to 1A7: Inverse Outputs of 0 to A7
Setting Value Function Description
100 to 1A7 Inverse Outputs of 0 to A7
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function to inversely
output.
For example, set H2-xx = 10E for the inverse output of E [Fault].
H3: Analog Inputs
WARNING! Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
Drives have three analog input terminals, terminals A1, A2, and A3. H3 parameters select the functions set to these
analog input terminals and adjust signal levels.
Table 12.64 shows the functions that you can set to analog input terminals. Use H3-02, H3-06, and H3-10 [MFAI
Function Selection] to set functions.
Table 12.64 MFAI Setting Values
Setting
Value
Function Ref.
0 Frequency Reference 936
1 Frequency Gain 936
2 Auxiliary Frequency Reference 1 936
3 Auxiliary Frequency Reference 2 937
4 Output Voltage Bias 937
5 Accel/Decel Time Gain 937
6 DC Injection Braking Current 937
7 Torque Detection Level 938
8 Stall Prevent Level During Run 938
9 Output Frequency Lower Limit 938
B PID Feedback 938
C PID Setpoint 939
D Frequency Bias 939
Setting
Value
Function Ref.
E Motor Temperature (PTC Input) 939
F Not Used 939
10 Forward Torque Limit 939
11 Reverse Torque Limit 940
12 Regenerative Torque Limit 941
13 Torque Reference / Torque Limit 941
14 Torque Compensation 941
15 General Torque Limit 941
16 Differential PID Feedback 941
1F Not Used 941
30 DWEZ Analog Input 1 941
31 DWEZ Analog Input 2 942
32 DWEZ Analog Input 3 942
Note:
All analog input scaling uses gain and bias for adjustment. Set the gain and bias values correctly.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents