12.8 H: Terminal Functions
942 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
■ 31: DWEZ Analog Input 2
Setting Value Function Description
31 DWEZ Analog Input 2
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
■ 32: DWEZ Analog Input 3
Setting Value Function Description
32 DWEZ Analog Input 3
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
◆ H4: Analog Outputs
H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias, and
select output signal levels.
■ Calibrate Meters Connected to MFAO Terminals FM and AM
To calibrate the meters connected to terminals FM and AM, use these parameters:
• H4-02 [Terminal FM Analog Output Gain]
• H4-03 [Terminal FM Analog Output Bias]
• H4-05 [Terminal AM Analog Output Gain]
• H4-06 [Terminal AM Analog Output Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use
jumper switch S5 and H4-07 [Terminal FM Signal Level Select] or H4-08 [Terminal AM Signal Level Select] to select
the voltage output and current output.
No. Name Range Default
H4-02 Terminal FM Analog Output Gain -999.9 - +999.9% 100.0%
H4-03 Terminal FM Analog Output Bias -999.9 - +999.9% 0.0%
H4-05 Terminal AM Analog Output Gain -999.9 - +999.9% 50.0%
H4-06 Terminal AM Analog Output Bias -999.9 - +999.9% 0.0%
H4-07 Terminal FM Signal Level Select
0: 0 to 10 Vdc
1: -10 to +10 Vdc
2: 4 to 20 mA
0
H4-08 Terminal AM Signal Level Select
0: 0 to 10 Vdc
1: -10 to +10 Vdc
2: 4 to 20 mA
0
Figure 12.110 and Figure 12.111 show the gain and bias.