12.9 L: Protection Functions
998 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Reduces the regenerative torque limit to the level set with L7-35 when using low frequencies such that the output
frequency is less than L7-36 [Regen Torque Limit Derate Freq]. The drive does not decrease torque limits during
ramp to stop operation. Decrease the setting of L7-35 when oC [Overcurrent] issues occur while a regenerative load
is input and the speed reference is constant.
Note:
Reduce the setting value of L7-35 in increments of 10.0% and reduce the setting value of L7-36 in increments of 2.0 Hz when faults occur
during regenerative loads at low speed.
Setting values that are too high can cause faults.
The torque limit reduction function does not operate when L7-35 is set with a value larger than L7-03 [Forward Regenerative Trq Limit] or
L7-04 [Reverse Regenerative Trq Limit].
The motor may rotate slightly faster than the reference when a regenerative load is input at low speeds while L7-35 is set to a low value.
L7-36: Regen Torque Limit Derate Freq
No.
(Hex.)
Name Description
Default
(Range)
L7-36
(1B58)
Expert
Regen Torque Limit Derate
Freq
Sets the frequency width at which L7-35 [Low Freq Regen Torque Limit Lvl] operates.
6.0 Hz
(0.0 - 30.0 Hz)
If the drive detects oC [Overcurrent] faults when you connect regenerative loads at low speed, increase the setting
value. Decreases the torque limit as specified by the setting of L7-35 in a range of 0 output frequency < L7-36.
When the torque limit gradually changes as specified by the output frequency until the output frequency = L7-36, the
value changes to the setting of L7-03 [Forward Regenerative Trq Limit] and L7-04 [Reverse Regenerative Trq Limit].
Note:
If you increase the setting of L7-36, the motor will rotate at a speed higher than specified when a you input a regenerative load. Do not set
the value higher than necessary.
L8: Drive Protection
L8 parameters set protective functions that prevent faults such as overheating, phase loss, and ground faults.
L8-01: 3% ERF DB Resistor Protection
No.
(Hex.)
Name Description
Default
(Range)
L8-01
(04AD)
3% ERF DB Resistor
Protection
Sets the function to enable braking resistor protection with a Yaskawa ERF series braking resistor
(3% ED) installed on the heatsink.
0
(0, 1)
0 : Disabled
Disables braking resistor protection. Use this setting for dynamic braking options that are not Yaskawa ERF series
braking resistors.
1 : Enabled
Enables protection for Yaskawa ERF series braking resistors.
Note:
Set L8-01 = 1 and H2-01 to H2-03 = D [MFDO Function Select = Braking Resistor Fault]. Use a sequence to turn OFF power with MFDO.
L8-02: Overheat Alarm Level
No.
(Hex.)
Name Description
Default
(Range)
L8-02
(04AE)
Overheat Alarm Level
Sets the oH detection level in temperature.
Determined by o2-04, C6-01
(50 - 150 °C)
If the heatsink temperature is more than the temperature set in this parameter, the drive detects an overheat pre-alarm.
To enable this function, set one of H2-01 to H2-03 [MFDO Function Select] to 20 [Drive Overheat Pre-Alarm (oH)].
If the temperature increases to the overheat fault level, the drive will trigger an oH1 [Heatsink Overheat] fault and
stop operation.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV