Parameter Details
12
12.12 T: Auto-Tuning
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 1057
12.12 T: Auto-Tuning
Numbers identifying the T parameters are displayed when an LED keypad is used. The names of the parameters are
displayed on the LCD screen of the LCD keypad. Set the following.
Induction Motor Auto-Tuning
PM Motor Auto-Tuning
ASR and Inertia Tuning
T0: Tuning Mode Selection
T0-00: Tuning Mode Selection
No.
(Hex.)
Name Description
Default
(Range)
T0-00
(1197)
Tuning Mode Selection
Sets the type of Auto-Tuning.
0
(0, 1)
When you use an LED keypad to do Control Tuning, set the tuning mode in this order:
1. Set T0-00 = 1.
2. Set T3-00 [Control Loop Tuning Selection] to set the tuning mode.
Note:
The available tuning modes are different for different control methods.
0 : Motor Parameter Tuning
1 : Control Tuning
T1: Induction Motor Auto-Tuning
T1 parameters set the Auto-Tuning input data for induction motor tuning.
Note:
The base frequency of drive dedicated motors and special motors for use with vector control may be lower than the base frequency of
general-purpose motors, which is 50 Hz or 60 Hz. In such cases, this lower frequency is used as the value for E1-06 [Base Frequency] and
E1-04 [Maximum Output Frequency] after Auto-Tuning completes. If the maximum output frequency is too low and causes problems,
change the setting of E1-04 after Auto-Tuning completes.
The following induction motor parameters are set automatically.
E1-xx [V/f Pattern for Motor 1]
E2-xx [Motor Parameters]
E3-xx [V/f Pattern for Motor 2]
E4-xx [Motor 2 Parameters]
F1-xx [Encoder Options] (only with Closed Loop Vector Control)
T1-00: Motor 1/Motor 2 Selection
No.
(Hex.)
Name Description
Default
(Range)
T1-00
(0700)
Motor 1/Motor 2 Selection
Sets which motor to tune when motor 1/2 switching is enabled.
1
(1, 2)
Note:
This parameter is available when H1-xx = 16 [Motor 2 Selection]. The keypad will not show this parameter when H1-xx 16.
1 : Motor 1 (sets E1-xx, E2-xx)
Auto-Tuning automatically sets parameters E1-xx and E2-xx for motor 1.
2 : Motor 2 (sets E3-xx, E4-xx)
Auto-Tuning automatically sets parameters E3-xx and E4-xx for motor 2. Make sure that you connect motor 2 to the
drive for Auto-Tuning.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV