Parameter List
11
11.8 E: Motor Parameters
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 569
◆ E9: Motor Setting
No.
(Hex.)
Name Description
Default
(Range)
Ref.
E9-01
(11E4)
Motor Type Selection
Sets the type of motor.
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
0
(0 - 2)
836
E9-02
(11E5)
Maximum Speed
Sets the maximum speed of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
836
E9-03
(11E6)
Rated Speed
Sets the rated rotation speed of the motor.
Determined by E9-01
(100 - 7200 min
-1
)
836
E9-04
(11E7)
Base Frequency
Sets the rated frequency of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
836
E9-05
(11E8)
Motor Rated Voltage
Sets the rated voltage of the motor.
200 V Class: 230.0 V,
400 V Class: 460.0 V
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
837
E9-06
(11E9)
Motor Rated Current
(FLA)
Sets the motor rated current in amps.
Determined by E9-01 and
o2-04
(10% to 200% of the
drive rated current)
837
E9-07
(11EA)
Motor Rated Power
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
Determined by E9-02 and
o2-04
(0.00 - 650.00 kW)
837
E9-08
(11EB)
Motor Pole Count
Sets the number of motor poles.
4
(2 to 120)
837
E9-09
(11EC)
Motor Rated Slip
Sets the motor rated slip.
0.000 Hz
(0.000 - 20.000 Hz)
837
E9-10
(11ED)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
838