12.8 H: Terminal Functions
904 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
7E: Reverse Rotation Identifier
Setting Value Function Description
7E Reverse Rotation Identifier
Sets the rotation direction of the motor when in Simple Closed Loop V/f Control method and F1-21, F1-37 = 0 [Encoder Option
Function Selection = A pulse detection], or when in Closed Loop V/f Control method.
ON : Reverse run
The drive knows that the motor is rotating in reverse .
OFF : Forward run
The drive knows that the motor is rotating forward .
90 to 97: DriveWorksEZ Digital Inputs 1 to 8
Setting Value Function Description
90 - 97 DWEZ Digital Inputs 1 to 8
Sets digital inputs used with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
Note:
You cannot set values 90 to 97 for inverse output.
9F: DWEZ Disable
Setting Value Function Description
9F DWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Enabled/Disabled wDigital Input] to use this function.
ON : Disabled
OFF : Enabled
101 to 19F: Inverse Input of 1 to 9F
Setting Value Function Description
101 to 19F Inverse Inputs of 1 to 9F Sets the function of the selected MFDI to operate inversely. To select the function, enter 1xx, where the xx is the function setting
value.
For example, to use the inverse input of E [ASR Integral Reset], set H1-xx = 10E.
Note:
You cannot use inverse input for all functions. Refer to Table 12.55 for more information.
H2: MFDO
H2 parameters set the MFDO terminal functions.
H2-01 to H2-03 Terminal M1-M2, M3-M4, M5-M6 Function Selection
The drive has three MFDO terminals. Table 12.60 shows the default function settings for the terminals.
Table 12.60 MFDO Terminals Default Function Settings
No. Name Default Function
H2-01 Term M1-M2 Function Selection 0 During Run
H2-02 Term M3-M4 Function Selection 1 Zero Speed
H2-03 Terminal M5-M6 Function Select 2 Speed Agree 1
Refer to Table 12.61 to set H2-xx [MFDO Function Select].
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV