Parameter List
11
11.20 Parameters Changed by E1-03 [V/f Pattern Selection]
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 669
11.20 Parameters Changed by E1-03 [V/f Pattern Selection]
The values for parameters A1-02 [Control Method Selection] and E1-03 [V/f Pattern Selection] change the default
settings for the parameters in these tables:
Table 11.1 Parameters Changed by E1-03: 2004 to 2021 (HD), 4002 to 4018 (ND), 4002 to 4012 (HD), and 4002 to 4009 (ND)
No. E1-03 E1-04 E1-05
*1
E1-06 E1-07 E1-08
*1
E1-09 E1-10
*1
Unit - Hz V Hz Hz V Hz V
Setting Value
0 50.0 230.0 50.0 2.5 17.3 1.3 10.4
1 60.0 230.0 60.0 3.0 17.3 1.5 10.4
2 60.0 230.0 50.0 3.0 17.3 1.5 10.4
3 72.0 230.0 60.0 3.0 17.3 1.5 10.4
4 50.0 230.0 50.0 25.0 40.3 1.3 9.2
5 50.0 230.0 50.0 25.0 57.5 1.3 10.4
6 60.0 230.0 60.0 30.0 40.3 1.5 9.2
7 60.0 230.0 60.0 30.0 57.5 1.5 10.4
8 50.0 230.0 50.0 2.5 21.9 1.3 12.7
9 50.0 230.0 50.0 2.5 27.6 1.3 15.0
A 60.0 230.0 60.0 3.0 21.9 1.5 12.7
B 60.0 230.0 60.0 3.0 27.6 1.5 17.3
C 90.0 230.0 60.0 3.0 17.3 1.5 10.4
D 120.0 230.0 60.0 3.0 17.3 1.5 10.4
E 180.0 230.0 60.0 3.0 17.3 1.5 10.4
F 60.0
*2
230.0
*2
60.0
*2
3.0
*2
17.3
*2
1.5
*2
10.2
*2
Control Method
Selection
(A1-02 Setting)
OLV (2) 60.0 230.0 60.0 3.0 13.8 0.5 2.9
CLV (3) 60.0 230.0 60.0 0.0 0.0 0.0 0.0
OLV/PM (5)
*3 *3 *3
- -
*3
-
AOLV/PM (6)
*3 *3 *3
- -
*3
-
CLV/PM (7)
*3 *3 *3
- - 0.0 -
*1 This is the value for 200 V class drives. Double the value for 400 V class drives.
*2 These values are the default settings for E1-04 to E1-10 and E3-04 to E3-10 [V/f Pattern for Motor 2]. These settings are the same as
those for the V/f pattern when E1-03 = 1 [Const Trq, 60Hz base, 60Hz max].
*3 The default setting varies depending on the setting of E5-01 [PM Motor Code Selection].