Electrical Installation
3
3.12 Improve the Power Factor
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 143
3.12 Improve the Power Factor
Connect an AC Reactor or a DC Link Choke
AC reactors and DC link chokes decrease surges in current and improve the power factor on the input side of the
drive.
Connect an AC reactor or a DC link choke the input side (primary side) in the these conditions:
To decrease harmonic current or improve the power factor of the power supply
When there is switching of phase advancing capacitor
With a large capacity power supply transformer (600 kVA or more).
Note:
You can use an AC reactor and DC link choke together.
When you connect a thyristor converter (for example, a DC drive) to the same power supply system, use an AC reactor.
The main circuit terminal block for the drive, and the terminal blocks for the AC reactor and DC Link Choke come in different shapes. The
drive has a European-style terminal block, and the AC reactor and DC Link Choke have a circular terminal block. Correctly prepare the
ends of the wiring.
Ground the AC reactor and DC Link Choke (option) on the back of the mounting base. Remove all paint from the mounting surface of the
control panel.
Connect an AC Reactor
Note:
When you connect an AC reactor to the output side (secondary side) of the driver, set C6-02 = 1 [Carrier Frequency Selection = 2.0 kHz].
A - Power Supply
B - MCCB
C - AC reactor
D - Drive
Figure 3.89 AC Reactor Connection Example
Connect a DC Link Choke
When you install a DC link choke, remove the jumper between terminals +1 and +2. If you will not use a DC link
choke, do not remove the jumper. Refer to Figure 3.90 for an example of how to wire the DC link choke.
A - Power supply
B - MCCB
C - Drive
D - DC link choke
Figure 3.90 DC Link Choke Connection Example