4.6 Keypad Operation
190 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Save a Backup of Parameters
You can save a backup of the drive parameters to the keypad. The keypad can store parameter setting values for a
maximum of four drives in different storage areas. Backups of the parameter settings can save time when you set
parameters after you replace a drive. When you set up more than one drive, you can copy the parameter settings from
a drive that completed a test run to the other drives.
Note:
Stop the motor before you back up parameters.
The drive will not accept a Run command while it makes a backup.
The DriveWorksEZ PC software password is necessary to back up qx-xx [DriveWorksEZ Parameter] and rx-xx [DWEZ Connection
Parameter]. If you enter an incorrect password, the drive detects PWEr [DWEZ Password Missmatch].
1. Push [Home] to show the HOME screen.
Note:
When the drive is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen.
If [Home] is not shown on , push (Back) to show [Home] on .
2. Push (Menu).
3. Push or to select [Parameter Backup/Restore], then push .
4. Push or to select the items to back up, then push .
5. Push or to select [Backup (drive keypad)], then push .