EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Startup Procedure and Test Run
4
4.3 LED Status Ring
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 165
4.3 LED Status Ring
The LED Status Ring on the drive cover shows the drive operating status.
A - ALM/ERR
B - Ready
C - RUN
LED Status Description
A ALM/ERR
Illuminated
The drive detects a fault.
Flashing
*1
The drive detects:
An alarm
An oPE parameter setting error
An Auto-Tuning error
Note:
The LED will illuminate to identify a fault if the drive detects a fault and an alarm at the same time.
OFF
There are no drive faults or alarms.
B Ready
Illuminated
The drive is operating or is prepared for operation.
Flashing
*1
The drive is in STo [Safe Torque OFF] condition.
Flashing Quickly
*1
The voltage of the main circuit power supply dropped, and only the external 24 V power supply provides the power to the
drive.
OFF
The drive detects a fault.
There is no fault and the drive received a Run command, but the drive cannot operate. For example, in Programming
Mode or when is flashing.
C RUN
Illuminated
The drive is in regular operation.
Flashing
*1
The drive is decelerating to stop.
The drive received a Run command with a frequency reference of 0 Hz, but the drive is not set for zero speed control.
The drive received a DC Injection Braking command.
Flashing Quickly
*1
The drive received a Run command from the MFDI terminals and is switching to REMOTE Mode while the drive is in
LOCAL Mode.
The drive received a Run command from the MFDI terminals when the drive is not in Drive Mode.
The drive received a Fast Stop command.
The safety function shuts off the drive output.
The user pushed on the keypad while the drive is operating in REMOTE Mode.
The drive is energized with an active Run command and b1-17 = 0 [Run Command at Power Up = Disregard Existing
RUN Command].
The drive is set to coast-to-stop with timer (b1-03 = 3 [Stopping Method Selection = Coast to Stop with Timer]), and the
Run command is disabled then enabled during the Run wait time.
OFF
The motor is stopped.
*1 Refer to Figure 4.6 for the difference between flashing and flashing quickly.