Parameter List
11
11.5 b: Application
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 551
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b5-95
(0B95)
EZ Sleep Wake-up Mode
Sets the wake-up mode to use when exiting Sleep Mode.
0 : Absolute
1 : Setpoint Delta
0
(0, 1)
760
b5-96
(0B96)
RUN
EZ Sleep Wake-up Time
Sets the EZ Wake-up time.
1.0 s
(0.0 - 1000.0 s)
760
◆ b6: Dwell Function
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b6-01
(01B6)
Dwell Reference at Start
Sets the output frequency that the drive will hold momentarily when the motor starts.
0.0
(Determined by A1-02)
761
b6-02
(01B7)
Dwell Time at Start
Sets the length of time that the drive will hold the output frequency when the motor starts.
0.0 s
(0.0 - 10.0 s)
761
b6-03
(01B8)
Dwell Reference at Stop
Sets the output frequency that the drive will hold momentarily when ramping to stop the
motor.
0.0
(Determined by A1-02)
761
b6-04
(01B9)
Dwell Time at Stop
Sets the length of time for the drive to hold the output frequency when ramping to stop the
motor.
0.0 s
(0.0 - 10.0 s)
761
◆ b7: Droop Control
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b7-01
(01CA)
RUN
Droop Control Gain
Sets the amount of deceleration when the torque reference is at 100% as a percentage of
E1-04 [Maximum Output Frequency].
0.0%
(0.0 - 100.0%)
762
b7-02
(01CB)
RUN
Droop Control Delay
Time
Sets the responsiveness of Droop control. Decrease this setting when drive response is
slow. Increase this setting when hunting or oscillation occur.
0.05 s
(0.03 - 2.00 s)
762
b7-03
(017E)
Droop Control Limit
Selection
Sets the Droop control limit function.
0 : Disabled
1 : Enabled
1
(0, 1)
762
◆ b8: Energy Saving
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b8-01
(01CC)
Energy Saving Control
Selection
Sets the Energy-saving control function.
0 : Disabled
1 : Enabled
2 : Automatic Optimization
Note:
Setting 2 is available only when A1-02 = 6, 7 [Control Method Selection = AOLV/PM,
CLV/PM] and in Expert Mode.
0
(0 - 2)
763
b8-02
(01CD)
RUN
Expert
Energy Saving Gain
Sets the gain for Energy-saving control.
Determined by A1-02
(0.0 - 10.0)
763
b8-03
(01CE)
RUN
Expert
Energy Saving Filter
Time
Sets the responsiveness for Energy-saving control.
Determined by A1-02,
C6-01 and o2-04
(0.00 - 10.00 s)
763