11.10 H: Terminal Functions
606 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Setting Value Function Description Ref.
191 !DWEZ Digital Output 2
Sets the DriveWorksEZ digital output 2. Refer to the DriveWorksEZ online manual for more information.
929
192 !DWEZ Digital Output 3
Sets the DriveWorksEZ digital output 3. Refer to the DriveWorksEZ online manual for more information.
929
193 !DWEZ Digital Output 4
Sets the DriveWorksEZ digital output 4. Refer to the DriveWorksEZ online manual for more information.
929
1A0 !DWEZ Extended Digital
Output 1
Sets the digital output 1 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more
information.
929
1A1 !DWEZ Extended Digital
Output 2
Sets the digital output 2 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more
information.
929
1A2 !DWEZ Extended Digital
Output 3
Sets the digital output 3 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more
information.
929
1A3 !DWEZ Extended Digital
Output 4
Sets the digital output 4 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more
information.
929
1A4 !DWEZ Extended Digital
Output 5
Sets the digital output 5 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more
information.
929
1A5 !DWEZ Extended Digital
Output 6
Sets the digital output 6 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more
information.
929
1A6 !DWEZ Extended Digital
Output 7
Sets the digital output 7 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more
information.
929
1A7 !DWEZ Extended Digital
Output 8
Sets the digital output 8 for the DriveWorksEZ DO-A3 option. Refer to the DriveWorksEZ online manual for more
information.
929
◆ H3: Analog Inputs
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0 : 0-10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
931
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1.
0
(0 - 32)
931
H3-03
(0411)
RUN
Terminal A1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
931
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
932
H3-05
(0413)
Terminal A3 Signal Level
Select
Sets the input signal level for MFAI terminal A3.
0 : 0-10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
932
H3-06
(0414)
Terminal A3 Function
Selection
Sets the function for MFAI terminal A3.
2
(0 - 32)
932
H3-07
(0415)
RUN
Terminal A3 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A3.
100.0%
(-999.9 - +999.9%)
933