Parameter Details
12
12.8 H: Terminal Functions
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 907
Note:
When you use the function to output logical calculation results, you cannot set H2-01 to H2-03 = 1xx [Inverse Output of xx]. If you do, the
drive will detect oPE33 [Digital Output Selection Error].
When you do not use H2-60, H2-63, and H2-66, set them to F. The through mode function is not supported.
H2 MFDO Parameters
H2-01: Term M1-M2 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-01
(040B)
Term M1-M2 Function
Selection
Sets the function for MFDO terminal M1-M2.
0
(0 - 1FF)
Note:
When you do not use the terminal or when you use the terminal in through mode, set this parameter to F.
H2-02: Term M3-M4 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-02
(040C)
Term M3-M4 Function
Selection
Sets the function for MFDO terminal M3-M4.
1
(0 - 1FF)
Note:
When you do not use the terminal or when you use the terminal in through mode, set this parameter to F.
H2-03: Term M5-M6 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-03
(040D)
Term M5-M6 Function
Selection
Sets the function for MFDO terminal M5-M6.
2
(0 - 1FF)
Note:
When you do not use the terminal or when you use the terminal in through mode, set this parameter to F.
H2-06: Watt Hour Output Unit Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output].
0
(0 - 4)
This output is input to the Watt hour meter or PLC through a 200 ms pulse signal. This parameter sets the kWh unit
for each pulse output.
Figure 12.88 Example MFDO when Configured for Watt Hours
Note:
When the power value is a negative value (regenerative state), the drive does not count Watt hours.
When the control power supply to the drive is operating, the drive will keep the Watt hours. If a momentary power loss causes the drive to
lose control power, the Watt hour count will reset.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV