Parameter Details
12
12.11 o: Keypad-Related Settings
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 1043
o2: Keypad Operation
o2-01: LO/RE Key Function Selection
No.
(Hex.)
Name Description
Default
(Range)
o2-01
(0505)
LO/RE Key Function
Selection
Sets the function that lets you use to switch between LOCAL and REMOTE Modes.
1
(0, 1)
0 : Disabled
You cannot use to switch between LOCAL and REMOTE Modes.
1 : Enabled
You can use to switch between LOCAL and REMOTE Modes when the drive is stopped. When LOCAL Mode
is selected, on the keypad will come on.
WARNING! Sudden Movement Hazard. If you change the control source when b1-07 = 1 [LOCAL/REMOTE Run Selection = Accept
Existing RUN Command], the drive can start suddenly. Before you change the control source, remove all personnel from the area
around the drive, motor, and load. Sudden starts can cause serious injury or death.
WARNING! Sudden Movement Hazard. Fully examine all mechanical and electrical connections before you change o2-01 [LO/RE
Key Function Selection] or b1-07 [LOCAL/REMOTE Run Selection]. Sudden starts can cause serious injury or death. If b1-07 = 1
[Accept Existing RUN Command] and there is an active Run command when you switch from LOCAL to REMOTE Mode, the drive
can start suddenly.
Table 12.73 Function Settings with o2-01 and b1-07
Function Selection
LOCAL/REMOTE Run Selection
Switching from LOCAL Mode to
REMOTE Mode
Switching from REMOTE Mode to
LOCAL Mode
o2-01 = 0 [Disabled] b1-07 = 0 [Disregard Existing RUN
Command]
The drive will not switch modes. The drive will not switch modes.
b1-07 = 1 [Accept Existing RUN
Command]
o2-01 = 1 [Enabled] b1-07 = 0 [Disregard Existing RUN
Command]
The drive will not start operating although
the Run command is active. When you set
Run command to active again, the drive will
start to run.
The drive cannot operate because the Run
command is not enabled.
b1-07 = 1 [Accept Existing RUN
Command]
When the Run command is active, the drive
will start to run immediately when the mode
switches from LOCAL to REMOTE.
The drive cannot operate because the Run
command is not enabled.
o2-02: STOP Key Function Selection
No.
(Hex.)
Name Description
Default
(Setting Range)
o2-02
(0506)
STOP Key Function
Selection
Sets the function to use on the keypad to stop the drive when the Run command source for
the drive is REMOTE (external) and not assigned to the keypad.
1
(0, 1)
0 : Disabled
1 : Enabled
stays enabled when the Run command source has not been assigned to the keypad.
To start the drive again after you push to stop operation, turn the external Run command OFF and ON again.
o2-03: User Parameter Default Value
No.
(Hex.)
Name Description
Default
(Range)
o2-03
(0507)
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults to use during
initialization.
0
(0 - 2)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals