5.3 UL Standards
294 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Drive Motor Overload and Overheat Protection
The drive motor overload and overheat protection function complies with the National Electric Code (NEC) and the
Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and L1-01 through L1-04 [Motor Overload Protection Select] correctly to enable motor
overload and overheat protection.
Refer to the control method and set the motor rated current with E2-01 [Motor Rated Current (FLA)], E5-03 [PM
Motor Rated Current (FLA)], or E9-06 [Motor Rated Current (FLA)].
E2-01: Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E2-01
(030E)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by o2-04, C6-01
(10% to 200% of the drive
rated current)
Note:
If E2-01 < E2-03 [Motor No-Load Current], the drive will detect oPE02 [Parameter Range Setting Error].
When the drive model changes, the display units for this parameter also change.
0.01 A: models 2004 - 2042, 4002 - 4023
0.1 A: models 2056 - 2415, 4031 - 4720, T103 - T720
The value set for E2-01 becomes the reference value for motor protection, the torque limit, and torque control. Enter
the motor rated current written on the motor nameplate. Auto-Tuning the drive will automatically set E2-01 to the
value input for Motor Rated Current.
E5-03: Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E5-03
(032B)
Motor Rated Current (FLA)
Sets the PM motor rated current (FLA).
Determined by E5-01
(10% to 200% of the drive
rated current)
Note:
The display units are different for different models:
0.01 A: models 2004 - 2042, 4002 - 4023
0.1 A: models 2056 - 2415, 4031 - 4720, T103 - T720
The drive automatically sets E5-03 to the value input for PM Motor Rated Current after you do these types of Auto-
Tuning:
Manual Entry w/ Motor Data Sheet
PM Stationary Auto-Tuning
Stationary (R Only)
Rotational (Ld, Lq, R, back-EMF)
E9-06: Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E9-06
(11E9)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by E9-01 and
o2-04
(10% to 200% of the drive
rated current)
Note:
The display units are different for different models:
0.01 A: models 2004 - 2042, 4002 - 4023
0.1 A: models 2056 - 2415, 4031 - 4720, T103 - T720
The setting value of E9-06 is the reference value for motor protection. Enter the motor rated current written on the
motor nameplate. Auto-Tuning the drive will automatically set E9-06 to the value input for Motor Rated Current.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals