11.17 U: Monitors
652 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
No.
(Hex.)
Name Description MFAO Signal Level
U3-16
(080F)
ElapsedTime@6thFault
Shows the cumulative operation time when the sixth most recent fault occurred.
Unit: 1 h
No signal output available
U3-17
(0810)
ElapsedTime@7thFault
Shows the cumulative operation time when the seventh most recent fault occurred.
Unit: 1 h
No signal output available
U3-18
(0811)
ElapsedTime@8thFault
Shows the cumulative operation time when the eighth most recent fault occurred.
Unit: 1 h
No signal output available
U3-19
(0812)
ElapsedTime@9thFault
Shows the cumulative operation time when the ninth most recent fault occurred.
Unit: 1 h
No signal output available
U3-20
(0813)
ElapsedTime@10 Fault
Shows the cumulative operation time when the tenth most recent fault occurred.
Unit: 1 h
No signal output available
◆ U4: Maintenance Monitors
No.
(Hex.)
Name Description MFAO Signal Level
U4-01
(004C)
Cumulative Ope Time
Shows the cumulative operation time of the drive.
Use parameter o4-01 [Elapsed Operating Time Setting] to reset this monitor. Use parameter o4-02
[Elapsed Operating Time Selection] to select the cumulative operation times from:
• The time from when the drive is energized until it is de-energized.
• The time at which the Run command is turned ON.
The maximum value that the monitor will show is 99999. After this value is more than 99999, the
drive automatically resets it and starts to count from 0 again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 0099H for
data in 1 h units.
10 V: 99999 h
U4-02
(0075)
Num of Run Commands
Shows how many times that the drive has received a Run command.
Use parameter o4-13 [RUN Command Counter @ Initialize] to reset this monitor. The maximum
value that the monitor will show is 65535. After this value is more than 65535, the drive
automatically resets it and starts to count from 0 again.
Unit: 1
10 V: 65535 times
U4-03
(0067)
Cooling Fan Ope Time
Shows the cumulative operation time of the cooling fans.
Use parameter o4-03 [Fan Operation Time Setting] to reset this monitor. The maximum value that
the monitor will show is 99999. After this value is more than 99999, the drive automatically resets it
and starts to count from 0 again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 009BH for
data in 1 h units.
10 V: 99999 h
U4-04
(007E)
Cool Fan Maintenance
Shows the cumulative operation time of the cooling fans as a percentage of the replacement life of
the cooling fans.
Use parameter o4-03 [Fan Operation Time Setting] to reset this monitor.
Unit: 1%
Note:
Replace the cooling fans when this monitor is 90%.
10 V: 100%
U4-05
(007C)
CapacitorMaintenance
Shows the operation time of the electrolytic capacitors for the main circuit and control circuit as a
percentage of the replacement life of the electrolytic capacitors.
Use parameter o4-05 [Capacitor Maintenance Setting] to reset this monitor.
Unit: 1%
Note:
Replace the electrolytic capacitor when this monitor is 90%.
10 V: 100%