11.9 F: Options
574 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F3-22
(0BEF)
Expert
Terminal DC Function
Selection
Sets the function for terminal DC of the DI-A3 option when F3-01 = 8 [Digital Input
Function Selection = Multi-Function Digital Input].
F
(1 - 19F)
853
F3-23
(0BF0)
Expert
Terminal DD Function
Selection
Sets the function for terminal DD of the DI-A3 option when F3-01 = 8 [Digital Input
Function Selection = Multi-Function Digital Input].
F
(1 - 19F)
853
F3-24
(0BF1)
Expert
Terminal DE Function
Selection
Sets the function for terminal DE of the DI-A3 option when F3-01 = 8 [Digital Input
Function Selection = Multi-Function Digital Input].
F
(1 - 19F)
853
F3-25
(0BF2)
Expert
Terminal DF Function
Selection
Sets the function for terminal DF of the DI-A3 option when F3-01 = 8 [Digital Input
Function Selection = Multi-Function Digital Input].
F
(1 - 19F)
853
◆ F4: Analog Output Option
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F4-01
(0391)
Terminal V1 Function
Selection
Sets the monitor signal output from terminal V1.
Set the x-xx part of the Ux-xx [Monitor]. For example, set F4-01 = 102 to monitor U1-02
[Output Frequency].
102
(000 - 999)
854
F4-02
(0392)
RUN
Terminal V1 Gain
Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal
output level from the terminal V1 at 10 Vor 20 mA as 100% when an output for
monitoring items is 100%.
100.0%
(-999.9 - +999.9%)
854
F4-03
(0393)
Terminal V2 Function
Selection
Sets the monitor signal output from terminal V2.
Set the x-xx part of the Ux-xx [Monitor]. For example, set F4-03 = 103 to monitor U1-03
[Output Current].
103
(000 - 999)
855
F4-04
(0394)
RUN
Terminal V2 Gain
Sets the gain of the monitor signal that is sent from terminal V2. Sets the analog signal
output level from terminal V2 at 10 Vor 20 mA as 100% when an output for monitoring
items is 100%.
50.0%
(-999.9 - +999.9%)
855
F4-05
(0395)
RUN
Terminal V1 Bias
Sets the bias of the monitor signal that is sent from terminal V1. When an output for
monitoring items is 0%, this parameter sets the analog signal output level from the V1
terminal as a percentage of 10 V or 20 mA.
0.0%
(-999.9 - +999.9%)
855
F4-06
(0396)
RUN
Terminal V2 Bias
Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the analog
signal sent from the V2 terminal at 10 Vor 20 mA as 100% when an output for monitoring
items is 0%.
0.0%
(-999.9 - +999.9%)
855
F4-07
(0397)
Terminal V1 Signal Level
Sets the output signal level for terminal V1.
0 : 0 to 10 V
1 : -10 to 10 V
0
(0, 1)
856
F4-08
(0398)
Terminal V2 Signal Level
Sets the output signal level for terminal V2.
0 : 0 to 10 V
1 : -10 to 10 V
0
(0, 1)
856
◆ F5: Digital Output Option
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F5-01
(0399)
Terminal P1-PC Function
Select
Sets the function of terminal P1-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3 Output
Mode Selection = Programmable (F5-01 to F5-08)] to enable this function.
0
(0 - 1A7)
857
F5-02
(039A)
Terminal P2-PC Function
Select
Sets the function of terminal P2-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3 Output
Mode Selection = Programmable (F5-01 to F5-08)] to enable this function.
1
(0 - 1A7)
857