Parameter Details
12
12.7 F: Options
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 857
Coded Output (Binary) Description
DO-A3 Terminal Block TB2
Terminal P1-PC Terminal P2-PC Terminal P3-PC Terminal P4-PC
4 oH, oH1 [Heatsink
Overheat]
0 0 1 0
5 oS [Overspeed] 1 0 1 0
6 Not used 0 1 1 0
7 rr [Dynamic Braking
Transistor Fault], rH
[Braking Resistor Overheat]
1 1 1 0
8 EF1 to EF8 [External Fault
(Terminals S1 to S8)]
0 0 0 1
9 CPFxx, oFAxx, oFbxx,
oFCxx [Drive Hardware
Fault]
*1
1 0 0 1
A oL1 [Motor Overload] 0 1 0 1
B Not used 1 1 0 1
C Uv1 [DC Bus
Undervoltage], Uv2 [Control
Power Undervoltage], Uv3
[Soft Charge Answerback
Fault]
0 0 1 1
D dEv [Speed Deviation] 1 0 1 1
E PGo [Encoder (PG)
Feedback Loss]
0 1 1 1
F Not used 1 1 1 1
*1 The xx characters are different for different faults.
Digital Output Card Selection
Refer to H2: Multi-function Digital Output for more information about the functions that output from the terminals
when F5-09 = 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to F5-08)]. Use F5-01 to F5-08 to set the
output items.
No. Name Setting Range Default
F5-01 Terminal P1-PC Function Select 0 - 192 0: During Run
F5-02 Terminal P2-PC Function Select 0 - 192 1: Zero Speed
F5-03 Terminal P3-PC Function Select 0 - 192 2: Speed Agree 1
F5-04 Terminal P4-PC Function Select 0 - 192 4: Frequency Detection 1
F5-05 Terminal P5-PC Function Select 0 - 192 6: Drive Ready
F5-06 Terminal P6-PC Function Select 0 - 192 37: During Frequency Output
F5-07 Terminal M1-M2 Function Select 0 - 192 F: Not Used
F5-08 Terminal M3-M4 Function Select 0 - 192 F: Not Used
F5-01: Terminal P1-PC Function Select
No.
(Hex.)
Name Description
Default
(Range)
F5-01
(0399)
Terminal P1-PC Function
Select
Sets the function of terminal P1-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3 Output Mode
Selection = Programmable (F5-01 to F5-08)] to enable this function.
0
(0 - 1A7)
F5-02: Terminal P2-PC Function Select
No.
(Hex.)
Name Description
Default
(Range)
F5-02
(039A)
Terminal P2-PC Function
Select
Sets the function of terminal P2-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3 Output Mode
Selection = Programmable (F5-01 to F5-08)] to enable this function.
1
(0 - 1A7)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV