Specifications
10
10.8 Drive Derating
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 505
Table 10.28 Carrier Frequency and Rated Current Derating When A1-02 = 4 [AOLV] (< 460 V)
Model
Rated Current (A)
Heavy Duty Rating (HD1)
C6-01 = 0
Normal Duty Rating (ND1)
C6-01 = 1
2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 2 kHz 4 kHz 6 kHz 8 kHz 10 kHz
T103 91.0 91.0 70.2 54.6 35.1 103 92.8 69.9 54.6 35.5
T140 112.0 95.2 65.0 44.8 - 140 101.1 62.0 36 -
T168 150.0 127.5 87.0 60.0 - 168 128.7 89.5 63 -
T208 180.0 153.0 104.4 72.0 - 208 144.3 80.6 38 -
T250 216.0 183.6 125.3 86.4 - 250 186.5 123.0 81 -
T302 260.0 221.0 150.8 104.0 - 302 227.2 152.5 103 -
T371 304.0 258.4 176.3 121.6 - 371 272.5 174.0 108 -
T414 371.0 315.4 215.2 148.4 - 414 316 216.9 151 -
T477 414.0 259.8 - - - 477 230 - - -
T568 477.0 299.3 - - - 568 274 - - -
T605 605.0 379.6 - - - 675 345 - - -
T720 605.0 379.6 - - - 720 368 - - -
Table 10.29 Carrier Frequency and Rated Current Derating When A1-02 = 6 [AOLV/ PM] (< 460 V)
Model
Rated Current (A)
Heavy Duty Rating (HD1)
C6-01 = 0
Normal Duty Rating (ND1)
C6-01 = 1
2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz
T103 91.0 91.0 85.8 70.2 54.6 39.0 103.0 100.5 85.2 69.9 54.6 39.3
T140 112.0 105.3 85.1 65.0 44.8 - 140.0 114.1 88.1 62.0 36.0 -
T168 150.0 141.0 114.0 87.0 60.0 - 168.0 141.8 115.6 89.5 63.3 -
T208 180.0 169.2 136.8 104.4 72.0 - 208.0 165.5 123.1 80.6 38.1 -
T250 216.0 203.0 164.2 125.3 86.4 - 250.0 207.7 165.3 123.0 80.6 -
T302 260.0 244.4 197.6 150.8 104.0 - 302.0 252.2 202.3 152.5 102.6 -
T371 304.0 285.8 231.0 176.3 121.6 - 371.0 305.3 239.7 174.0 108.3 -
T414 371.0 348.7 282.0 215.2 148.4 - 414.0 348.6 282.8 216.9 151.1 -
T477 414.0 311.3 - - - - 477.0 312.4 - - - -
T568 477.0 358.7 - - - - 568.0 372.0 - - - -
T605 605.0 455.0 - - - - 675.0 455.0 - - - -
T720 605.0 455.0 - - - - 720.0 485.3 - - - -
◆ Derating Depending on Ambient Temperature
When you install drives in a place where ambient temperatures are higher than the rated conditions or install drives
side-by-side in the enclosure panel, set L8-12 [Ambient Temperature Setting] and L8-35 [Installation Method
Selection]. Derate the output current as specified in Figure 10.1.