Parameter List
11
11.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 663
No. Name Range Unit
Control Method (A1-02 Setting)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
C5-06 ASR Delay Time 0.000 - 0.500 0.001 s - - - 0.004 0.004
C5-07
ASR Gain
Switchover
Frequency
0.0 - 400.0 0.1 Hz - - - 0.0 0.0
C6-02
Carrier Frequency
Selection
1 - F 1 1
*3
1
*3
1
*3
1 1
d3-01 Jump Frequency 1 0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
d3-02 Jump Frequency 2 0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
d3-03 Jump Frequency 3 0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
d3-04
Jump Frequency
Width
0.0 - 20.0 0.1 Hz 1.0 1.0 1.0 1.0 1.0
d5-02
Torque Reference
Delay Time
0 - 1000 1 ms - - - 0 0
E1-04
Maximum Output
Frequency
40.0 - 590.0
*3 *4
0.1 Hz 60.0
*5
60.0
*5
60.0 60.0 60.0
E1-05
Maximum Output
Voltage
0.0 - 255.0
*6
0.1 V 200.0
*5
200.0
*5
200.0 200.0 200.0
E1-06 Base Frequency 0.0 - 590.0
*4
0.1 Hz 60.0
*5
60.0
*5
60.0 60.0 60.0
E1-07
Mid Point A
Frequency
0.0 - 590.0
*7
0.1 Hz 3.0
*5
3.0
*5
3.0 - 0.0
E1-08
Mid Point A
Voltage
0.0 - 255.0
*6
0.1 V 15.0
*5
15.0
*5
11.0 - 0.0
E1-09
Minimum Output
Frequency
0.0 - 590.0
*4
0.1 Hz 1.5
*5
1.5
*5
0.5 0.0 0.0
E1-10
Minimum Output
Voltage
0.0 - 255.0
*6
0.1 V 9.0
*5
9.0
*5
2.0 - 0.0
E1-11
Mid Point B
Frequency
0.0 - 400.0 0.1 Hz 0.0 0.0 0.0 0.0 0.0
E1-12
Mid Point A
Voltage
0.0 - 255.0
*6
0.1 V 0.0 0.0 0.0 0.0 0.0
E1-13 Base Voltage 0.0 - 255.0
*6
0.1 V 0.0 0.0 0.0 0.0 0.0
F1-01
Encoder 1 Pulse
Count (PPR)
0 - 60000 1 ppr - 600 - 600 600
F1-05
Encoder 1
Rotation
Selection
0 - 1 1 - 0 - 0 0
F1-09
Overspeed
Detection Delay
Time
0.0 - 2.0 0.1 s - 1.0 - 0.0 0.1
L1-01
Motor Overload
(oL1) Protection
0 - 6 1 2 2 2 2 2
L2-31
KEB Start
Voltage Offset
Level
0 - 100
*6
1 V 0 0 0 0 0
L3-05
Stall Prevention
during RUN
0 - 3 1 2 2 - - -
L3-20
DC Bus Voltage
Adjustment Gain
0.00 - 5.00 0.01 1.00 1.00 0.30 0.30 0.30
L3-21
OVSuppression
Accel/Decel P
Gain
0.10 - 10.00 0.01 1.00 1.00 1.00 1.00 1.00
L3-36
Current
Suppression
Gain@Accel
0.0 - 100.0 0.1 10.0 10.0 20.0 - -
L4-01
Speed Agree
Detection Level
0.0 - 590.0
*4
0.1 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz
L4-02
Speed Agree
Detection Width
0.0 - 20.0 0.1 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz

Table of Contents