Parameter List
11
11.13 o: Keypad-Related Settings
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 635
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o1-45
(11C5)
RUN
3rd Monitor Area
Selection
Sets the horizontal axis value used to display the monitor set in o1-26 [Custom Monitor 3]
as a bar graph. This parameter is only available with an LCD keypad.
0 : +/- Area ( - o1-46 ~ o1-46 )
1 : + Area ( 0 ~ o1-46 )
0
(0 - 1)
1041
o1-46
(11C6)
RUN
3rd Monitor Area Setting
Sets the horizontal axis value used to display the monitor set in o1-26 [Custom Monitor 3]
as a bar graph. This parameter is only available with an LCD keypad.
100.0%
(0.0 - 100.0%)
1041
o1-47
(11C7)
RUN
Trend Plot 1 Scale
Minimum Value
Sets the horizontal axis minimum value used to display the monitor set in o1-24 [Custom
Monitor 1] as a trend plot. This parameter is only available with an LCD keypad.
-100.0%
(-300.0 - +299.9%)
1041
o1-48
(11C8)
RUN
Trend Plot 1 Scale
Maximum Value
Sets the maximum value for the vertical axis used to display the monitor that was set in o1-
24 [Custom Monitor 1] as a trend plot. This parameter is only available with an LCD
keypad.
100.0%
(-299.9 - +300.0%)
1041
o1-49
(11C9)
RUN
Trend Plot 2 Scale
Minimum Value
Sets the horizontal axis minimum value used to display the monitor set in o1-25 [Custom
Monitor 2] as a trend plot. This parameter is only available with an LCD keypad.
-100.0%
(-300.0 - +299.9%)
1041
o1-50
(11CA)
RUN
Trend Plot 2 Scale
Maximum Value
Sets the maximum value for the vertical axis used to display the monitor that was set in o1-
25 [Custom Monitor 2] as a trend plot. This parameter is only available with an LCD
keypad.
100.0%
(-299.9 - +300.0%)
1042
o1-51
(11CB)
RUN
Trend Plot Time Scale
Setting
Sets the time scale (horizontal axis) to display the trend plot. When you change this setting,
the drive automatically adjusts the data sampling time. This parameter is only available
with an LCD keypad.
300 s
(1 - 3600 s)
1042
o1-55
(11EE)
RUN
Analog Gauge Area
Selection
Sets the range used to display the monitor set in o1-24 [Custom Monitor 1] as an analog
gauge. This parameter is only available with an LCD keypad.
0 : +/- Area ( - o1-56 ~ o1-56 )
1 : + Area ( 0 ~ o1-56 )
1
( 0, 1 )
1042
o1-56
(11EF)
RUN
Analog Gauge Area
Setting
Sets the value used to display the monitor set in o1-24 [Custom Monitor 1] as an analog
meter. This parameter is only available with an LCD keypad.
100.0%
(0.0 - 100.0%)
1042
o1-58
(3125)
Motor Power Unit
Selection
Sets the setting unit for parameters that set the motor rated power.
0 : kW
1 : HP
1
(0, 1)
1042
◆ o2: Keypad Operation
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o2-01
(0505)
LO/RE Key Function
Selection
Sets the function that lets you use to switch between LOCAL and REMOTE
Modes.
0 : Disabled
1 : Enabled
1
(0, 1)
1043
o2-02
(0506)
STOP Key Function
Selection
Sets the function to use on the keypad to stop the drive when the Run command
source for the drive is REMOTE (external) and not assigned to the keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
1043
o2-03
(0507)
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults to
use during initialization.
0 : No change
1 : Set defaults
2 : Clear all
0
(0 - 2)
1043
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after replacing the control board.
Determined by the drive
(-)
1044