Parameter Details
12
12.6 E: Motor Parameters
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 825
E1-09: Minimum Output Frequency
No.
(Hex.)
Name Description
Default
(Range)
E1-09
(0308)
Minimum Output Frequency
Sets the minimum output frequency for the V/f pattern.
Determined by A1-02 and
E5-01
(Determined by A1-02, E1-
04, and E5-01)
E1-10: Minimum Output Voltage
No.
(Hex.)
Name Description
Default
(Range)
E1-10
(0309)
Minimum Output Voltage
Sets the minimum output voltage for the V/f pattern.
Determined by A1-02
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
E1-11: Mid Point B Frequency
No.
(Hex.)
Name Description
Default
(Range)
E1-11
(030A)
Expert
Mid Point B Frequency
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - E1-04)
Note:
Set this parameter to 0.0 to disable the function.
E1-12: Mid Point B Voltage
No.
(Hex.)
Name Description
Default
(Range)
E1-12
(030B)
Expert
Mid Point B Voltage
Sets a middle point voltage for the V/f pattern.
0.0 V
(200 V Class: 0.0 to 255.0 V,
400 V Class: 0.0 to 510.0 V)
Note:
Set this parameter to 0.0 to disable the function.
E1-13: Base Voltage
No.
(Hex.)
Name Description
Default
(Range)
E1-13
(030C)
Expert
Base Voltage
Sets the base voltage for the V/f pattern.
0.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 - 510.0
V)
Note:
After Auto-Tuning, the value of E1-13 = E1-05 [Maximum Output Voltage].
When E1-13 = 0.0, use the value of E1-05 to control the voltage.
E2: Motor Parameters
E2 parameters [Motor Parameters] are used to set induction motor data. To switch drive operation from one motor to
another motor, configure the first motor (motor 1).
Performing Auto-Tuning automatically sets the E2 parameters to the optimal values. If Auto-Tuning cannot be
performed, set the E2 parameters manually.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents