EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.7 F: Options
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 847
F1-52: Serial Encoder Comm Speed
No.
(Hex.)
Name Description
Default
(Range)
F1-52
(03D4)
Serial Encoder Comm Speed
Sets the communication speed between the PG-F3 option and the serial encoder.
0
(0 - 2)
Note:
This function is enabled when F1-50 = 1 or 2 [PG-F3 Option Encoder Type = EnDat Serial Only or HIPERFACE].
0 : 1M/9600bps
1 : 500k/19200bps
2 : 1M/38400bps
F2: Analog Input Option
F2 parameters set the operation of the drive when you use analog input option card AI-A3. The AI-A3 card has 3
input terminals that accept voltages of -10 V to +10 V (20 kΩ) or currents of 4 mA to 20 mA (250 Ω). Install the AI-
A3 card to enable setting very accurate analog references with high resolution.
Refer to the AI-A3 option manual for more information about how to install, wire, and set the AI-A3 card.
WARNING! Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
F2-01: Analog Input Function Selection
No.
(Hex.)
Name Description
Default
(Range)
F2-01
(038F)
Analog Input Function
Selection
Sets the input method for the analog reference used with AI-A3.
0
(0, 1)
Note:
When the AI-A3 card is not mounted in the drive, analog input terminals A1 to A3 on the drive are always enabled. The setting of this
parameter does not have an effect.
0 : 3 Independent Channels
Set F2-01 = 0 to increase the precision of A/D conversion when you use the functions for terminals A1 to A3 on the
drive as they are. You can input the MFAI signal from terminals V1 through V3 for AI-A3. The functions for
terminals A1, A2, and A3 on the drive are sent to terminals V1, V2, and V3 for AI-A3. Use gain and bias adjustment
when you input current to set signals to have negative numbers.
Note:
Set b1-01 = 1 [Frequency Reference Selection 1 = Analog Input] to set inputs individually.
If F2-01 = 0 and b1-01 = 3 [Option PCB], the drive will detect oPE05 [Run Cmd/Freq Ref Source Sel Err].
Figure 12.74 shows the individual input of analog inputs. H3-xx parameters set the function to input the analog
reference received from the AI-A3 card and to adjust the gain and bias of these signals.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals