12.7 F: Options
854 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
output voltage range of -10 V to +10 V. Install the AO-A3 card to a drive to output analog signals that monitor the
output status of the drive (output frequency and output current).
Refer to the AO-A3 card manual for more information about how to install, wire, and set the AO-A3 card.
Use the U monitor number to set the monitor data to be output from terminals V1 and V2 on the AO-A3 card. Enter
the last three digits of Ux-xx as the setting value.
Use Gain and Bias to Adjust the Output Signal Level of Terminal V1
You must stop the drive to adjust the output signal. Use this procedure to calibrate the drive:
1. View the F4-02 [Terminal V1 Gain] value on the keypad.
Terminal V1 will output a voltage = 100% of the monitor set in F4-01 [Terminal V1 Function Selection].
2. View the monitor connected to terminal V1 and adjust F4-02.
3. View the F4-05 [Terminal V1 Bias] value on the keypad.
Terminal V1 will output an analog signal = 100% of the parameter set in F4-01.
4. View the monitor connected to terminal V1 and adjust F4-05.
Use Gain and Bias to Adjust the Output Signal Level of Terminal V2
You must stop the drive to adjust the output signal. Use this procedure to calibrate the drive:
1. View the F4-04 [Terminal V2 Gain] value on the keypad.
Terminal V2 will output a voltage = 100% of the monitor set in F4-03 [Terminal V2 Function Selection].
2. View the monitor connected to terminal V2 and adjust F4-04.
3. View the F4-06 [Terminal V2 Bias] value on the keypad.
The analog signal equal to 0% of the parameter being set in F4-03 will be output from terminal V2.
4. View the monitor connected to terminal V2 and adjust F4-06.
F4-01: Terminal V1 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
F4-01
(0391)
Terminal V1 Function
Selection
Sets the monitor signal output from terminal V1.
102
(000 - 999)
Set the x-xx part of the Ux-xx [Monitors] to set monitor data to output from the option card. For example, set F4-01 =
102 to monitor U1-02 [Output Frequency].
Note:
You cannot use all of the monitors in all of the control methods.
When you use the terminal in through mode, set this parameter to 000 or 031. You can use MEMOBUS/Modbus communications or the
communication option to set the terminal V1 output level from the PLC.
F4-02: Terminal V1 Gain
No.
(Hex.)
Name Description
Default
(Range)
F4-02
(0392)
RUN
Terminal V1 Gain
Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal output level
from the terminal V1 at 10 V or 20 mA as 100% when an output for monitoring items is 100%.
100.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V1 is ±10 V. Use F4-07 [Terminal V1 Signal Level] to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage of
terminal V1 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V1 outputs a
maximum voltage of 10 V.
F4-01 [Terminal V1 Function Selection] = 102 (U1-02: Output Frequency)
F4-02 = 50.0%
F4-05 [Terminal V1 Bias] = 0.0%
F4-07 = 0 (0 V to 10 V)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV