12.8 H: Terminal Functions
908 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
■ H2-07: Modbus Register 1 Address Select
No.
(Hex.)
Name Description
Default
(Range)
H2-07
(0B3A)
Modbus Register 1 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets the address of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the bit
in H2-08 [Modbus Register 1 Bit Select].
■ H2-08: Modbus Register 1 Bit Select
No.
(Hex.)
Name Description
Default
(Range)
H2-08
(0B3B)
Modbus Register 1 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to Modbus Reg 1 Status Satisfied [H2-01 to H2-03 = 62] and uses the address
in H2-07 [Modbus Register 1 Address Select].
■ H2-09: Modbus Register 2 Address Select
No.
(Hex.)
Name Description
Default
(Range)
H2-09
(0B3C)
Modbus Register 2 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets H2-09 with the address of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63] and
uses the bit in H2-10 [Modbus Register 2 Bit Select].
■ H2-10: Modbus Register 2 Bit Select
No.
(Hex.)
Name Description
Default
(Range)
H2-10
(0B3D)
Modbus Register 2 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63] and uses the address
in H2-09.
■ H2-20: Comparator 1 Monitor Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-20
(1540)
Comparator 1 Monitor
Selection
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For example, set
H2-20 = 102 to monitor U1-02 [Output Frequency].
102
(000 - 999)
Note:
• For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
• The configurable monitor changes when the control method changes.