EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.8 H: Terminal Functions
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 909
H2-21: Comparator 1 Lower Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-21
(1541)
Comparator 1 Lower Limit
Sets the lower limit detection level for comparator 1 when the full scale analog output for the monitor
selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
H2-22: Comparator 1 Upper Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-22
(1542)
Comparator 1 Upper Limit
Sets the upper limit detection level for comparator 1 when the full scale analog output for the monitor
selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
H2-23: Comparator 1 Hysteresis
No.
(Hex.)
Name Description
Default
(Range)
H2-23
(1543)
Comparator 1 Hysteresis
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the
monitor selected in H2-20 [Comparator 1 Monitor Selection].
0.0%
(0.0 - 10.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
H2-24: Comparator 1 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-24
(1544)
Comparator 1 On-Delay
Time
Sets the on-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
H2-25: Comparator 1 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-25
(1545)
Comparator 1 Off-Delay
Time
Sets the off-delay time for comparator 1.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
H2-26: Comparator 2 Monitor Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-26
(1546)
Comparator 2 Monitor
Selection
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [Monitor]. For example, set
H2-26 = 103 to monitor U1-03 [Output Current].
103
(000 - 999)
Note:
The configurable monitor changes when the control method changes.
When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal output level from the PLC through
MEMOBUS/Modbus communications or the communication option.
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV