Parameter Details
12
12.8 H: Terminal Functions
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 927
■ 60: Internal Cooling Fan Failure
Setting Value Function Description
60 Internal Cooling Fan Failure
The terminal activates when the drive detects a cooling fan failure in the drive.
■ 61: Pole Position Detection Complete
Setting Value Function Description
61 Pole Position Detection
Complete
The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position of the PM motor.
■ 62: Modbus Reg 1 Status Satisfied
Setting Value Function Description
62 Modbus Reg 1 Status
Satisfied
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register address set with
H2-07 [Modbus Register 1 Address Select] activates.
■ 63: Modbus Reg 2 Status Satisfied
Setting Value Function Description
63 Modbus Reg 2 Status
Satisfied
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register address set with
H2-09 [Modbus Register 2 Address Select] activates.
■ 65: Standby Output
Setting Value Function Description
65 Standby Output
The terminal deactivates after the drive stops operating and after the time set with b8-51 [Standby Mode Wait Time].
ON : The Run command turns on and the magnetic contactor on the input side turns on.
OFF : The Run command turns off and the drive stops operating. Then, the magnetic contactor on
the input side turns off after the time set with b8-51 [Standby Mode Wait Time] elapses.
■ 66: Comparator1
Setting Value Function Description
66 Comparator1
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the values of H2-21
[Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24 [Comparator 1 On-Delay Time].