12.8 H: Terminal Functions
910 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
■ H2-27: Comparator 2 Lower Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-27
(1547)
Comparator 2 Lower Limit
Sets the lower limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
■ H2-28: Comparator 2 Upper Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-28
(1548)
Comparator 2 Upper Limit
Sets the upper limit detection level for comparator 2 as a percentage of the full scale analog output
for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
■ H2-29: Comparator 2 Hysteresis
No.
(Hex.)
Name Description
Default
(Range)
H2-29
(1549)
Comparator 2 Hysteresis
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for the
monitor selected in H2-26 [Comparator 2 Monitor Selection].
0.0%
(0.0 - 10.0%)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
■ H2-30: Comparator 2 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-30
(154A)
Comparator 2 On-Delay
Time
Sets the on-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
■ H2-31: Comparator 2 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-31
(154B)
Comparator 2 Off-Delay
Time
Sets the off-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.
■ H2-32: Comparator 1 Filter Time
No.
(Hex.)
Name Description
Default
(Range)
H2-32
(159A)
Comparator 1 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output of the
monitor selected with H2-20 [Comparator 1 Monitor Selection].
0.0s
(0.0 - 10.0 s)
Note:
For information on the comparator function, refer to 66: Comparator1 on page 927 and 67: Comparator2 on page 928.