EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.6 E: Motor Parameters
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 837
E9-05: Base Voltage
No.
(Hex.)
Name Description
Default
(Range)
E9-05
(11E8)
Motor Rated Voltage
Sets the rated voltage of the motor.
200 V Class: 230.0 V,
400 V Class: 460.0 V
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
EZ Tuning automatically sets this parameter to the value of [Base Voltage].
E9-06: Motor Rated Current (FLA)
No.
(Hex.)
Name Description
Default
(Range)
E9-06
(11E9)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by E9-01 and
o2-04
(10% to 200% of the drive
rated current)
Note:
The display units are different for different models:
0.01 A: models 2004 - 2042, 4002 - 4023
0.1 A: models 2056 - 2415, 4031 - 4720, T103 - T720
The setting value of E9-06 is the reference value for motor protection. Enter the motor rated current written on the
motor nameplate. Auto-Tuning the drive will automatically set E9-06 to the value input for Motor Rated Current.
E9-07: Motor Rated Power
No.
(Hex.)
Name Description
Default
(Range)
E9-07
(11EA)
Motor Rated Power
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
Determined by E9-02 and
o2-04
(0.00 - 650.00 kW)
Auto-Tuning automatically sets this parameter to the value of [Motor Rated Power (kW)].
E9-08: Motor Pole Count
No.
(Hex.)
Name Description
Default
(Range)
E9-08
(11EB)
Motor Pole Count
Sets the number of motor poles.
4
(2 to 120)
Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
E9-09: Motor Rated Slip
No.
(Hex.)
Name Description
Default
(Range)
E9-09
(11EC)
Motor Rated Slip
Sets the motor rated slip.
0.000 Hz
(0.000 - 20.000 Hz)
The setting value of this parameter is the slip compensation reference value.
The drive uses the setting values of E9-03, E9-04, and E9-08 to calculate this parameter. When Motor Rated Slip = 0,
Auto-Tuning automatically sets this parameter to the value of [Motor Rated Slip].
Note:
Set E9-01 = 0 [Motor Type Selection = Induction (IM)] before you set this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM