Parameter Details
12
12.10 n: Special Adjustment
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 1017
n4-68: Speed Estimation Filter Time
No.
(Hex.)
Name Description
Default
(Range)
n4-68
(1B88)
Speed Estimation Filter
Time
Sets the primary delay time constant for the speed estimation value. Usually it is not necessary to
change this setting.
0.001 s
(0.001 - 0.010 s)
If the motor speed oscillates in the high speed range, set the value to 0.010 s.
n4-69: Flux Control Response
No.
(Hex.)
Name Description
Default
(Range)
n4-69
(1B89)
Flux Control Response
Unifies control of magnetic flux to make motor vibrations more stable.
1.00
(0.00 - 60.00)
If step-out occurs when the load changes, decrease the setting value in 1.00 increments.
Note:
If heavy loads decrease motor speed, increase the setting value in 1.00 increments. If it does not get better, increase n4-74 [Limit of Flux
Loop] in 20% increments.
n4-70: Speed Command Comp @ Low Freq
No.
(Hex.)
Name Description
Default
(Range)
n4-70
(1B8A)
Speed Command Comp @
Low Freq
Sets the function to make the drive more stable when operating at low speeds. Usually it is not
necessary to change this setting.
1.00 Hz
(0.00 - 6.00 Hz)
This function makes the control more stable when you operate at low speeds.
If the load is light when the drive operates in the low speed range, increase the setting value in 0.3 Hz increments.
Note:
Increase the setting value to increase the stability when the drive is operating at low speed. It can make the speed control less accurate.
When the motor rotates faster than the frequency reference at low speed, decrease the setting value in 0.1 Hz
increments.
Note:
If you set the value too low, the motor can rotate in reverse.
n4-71: Flux Estimation Method
No.
(Hex.)
Name Description
Default
(Range)
n4-71
(1B8B)
Expert
Flux Estimation Method
Sets the flux estimation method. Usually it is not necessary to change this setting.
0
(0, 1)
0 : Method 1
1 : Method 2
n4-72: Speed Feedback Mode
No.
(Hex.)
Name Description
Default
(Range)
n4-72
(1B8C)
Speed Feedback Mode
Sets the requirement for an encoder option when A1-02 = 4 [Control Method Selection = Advanced
Open Loop Vector].
0
(0, 1)
You can connect a PG-B3 or PG-X3 encoder option in AOLV control. You can use the encoder option for better speed
control precision.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents