Parameter Details
12
12.10 n: Special Adjustment
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 1027
Note:
Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled] to enable this
parameter.
The drive automatically calculates this value when High Frequency Injection Auto-Tuning completes successfully.
n8-37: HFI Voltage Amplitude Level
No.
(Hex.)
Name Description
Default
(Range)
n8-37
(0564)
Expert
HFI Voltage Amplitude
Level
Sets the high frequency injection amplitude as a percentage where 200 V = 100% for 200 V class
drives and 400 V = 100% for a 400 V class drives. Usually it is not necessary to change this setting.
20.0%
(0.0 - 50.0%)
Note:
Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled] to enable this
parameter.
The drive automatically calculates this value when High Frequency Injection Auto-Tuning completes successfully.
n8-39: HFI LPF Cutoff Freq
No.
(Hex.)
Name Description
Default
(Range)
n8-39
(0566)
HFI LPF Cutoff Freq
Sets the low-pass filter shut-off frequency for high frequency injection.
250 Hz
(0 - 1000 Hz)
Note:
Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled] to enable this
parameter.
The drive automatically calculates this value when High Frequency Injection Auto-Tuning completes successfully.
n8-41: HFI P Gain
No.
(Hex.)
Name Description
Default
(Range)
n8-41
(0568)
Expert
HFI P Gain
Sets the response gain for the high frequency injection speed estimation.
2.5
(-10.0 - +10.0)
Note:
Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled] to enable this
parameter.
When A1-02= 6 [Control Method Selection = AOLV/PM] and you do High Frequency Injection Auto-Tuning, the drive automatically sets
this parameter .
Set n8-41 > 0.0 for IPM motors.
Set this parameter as follows.
If there is oscillation or hunting, decrease the setting in units of 0.5.
When it is necessary to track load changes, increase the setting in units of 0.5.
n8-42: HFI I Time
No.
(Hex.)
Name Description
Default
(Range)
n8-42
(0569)
Expert
HFI I Time
Sets the integral time constant for the high frequency injection speed estimation. Usually it is not
necessary to change this setting.
0.10 s
(0.00 - 9.99 s)
Note:
Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled] to enable this
parameter.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals