Parameter Details
12
12.10 n: Special Adjustment
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 1031
Note:
• It is not available with an SPM motor.
• The speed control range 1:100 is the momentary operation area. When you operate the motor continuously, make sure that the drive
capacity and motor capacity are acceptable.
■ n8-62: Output Voltage Limit Level
No.
(Hex.)
Name Description
Default
(Range)
n8-62
(057D)
Expert
Output Voltage Limit Level
Sets the output voltage limit to prevent saturation of the output voltage. Usually it is not necessary to
change this parameter.
200 V Class: 200.0 V,
400 V Class: 400.0 V
(200 V Class: 0.0 to 240.0 V,
400 V Class: 0.0 to 480.0 V)
Set this parameter lower than the input power supply voltage.
Note:
• When A1-02 = 7, 8 [Control Method Selection = CLV/PM, EZOLV], this parameter is available in Expert mode.
• When A1-02 = 8 [EZOLV], the default settings are:
–200 V Class: 230.0 V
–400 V Class: 460.0 V
■ n8-63: Output Voltage Limit P Gain
No.
(Hex.)
Name Description
Default
(Range)
n8-63
(057E)
Expert
Output Voltage Limit P Gain
Sets the proportional gain for output voltage control. Usually it is not necessary to change this
setting.
1.00
(0.00 - 100.00)
■ n8-64: Output Voltage Limit I Time
No.
(Hex.)
Name Description
Default
(Range)
n8-64
(057F)
Expert
Output Voltage Limit I Time
Sets the integral time for output voltage control. Usually it is not necessary to change this setting.
0.040 s
(0.000 - 5.000)
■ n8-65: Speed Fdbk Gain @ oV Suppression
No.
(Hex.)
Name Description
Default
(Range)
n8-65
(065C)
Expert
Speed Fdbk Gain @ oV
Suppression
Sets the gain of internal speed feedback detection suppression while the overvoltage suppression
function is operating as a magnification value. Usually it is not necessary to change this parameter.
1.50
(0.00 - 10.00)
Adjust this parameter in these conditions:
• If there is resonance or hunting when you use the overvoltage suppression function, increase the setting value.
• If motor response is low when you use the overvoltage suppression function, decrease the setting value in 0.05-unit
increments.
■ n8-66: Output Voltage Limit Filter Time
No.
(Hex.)
Name Description
Default
(Range)
n8-66
(0235)
Expert
Output Voltage Limit Filter
Time
Sets the filter time constant for output voltage control. Usually it is not necessary to change this
setting.
0.020 s
(0.000 - 5.000)