Parameter Details
12
12.11 o: Keypad-Related Settings
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 1051
o4-13: RUN Command Counter @ Initialize
No.
(Hex.)
Name Description
Default
(Range)
o4-13
(0528)
RUN Command Counter @
Initialize
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [Number of Runs (Low)], and
U4-25 [Number of Runs (High)].
0
(0, 1)
0 : No Reset
Keeps the monitor values for U4-02, U4-24, and U4-25.
1 : Reset
Resets the values of U4-02, U4-24, and U4-25. After the reset, the drive automatically resets o4-13 to 0.
o4-22: Time Format
No.
(Hex.)
Name Description
Default
(Range)
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available when using an LCD keypad.
1
(0 - 2)
Sets the display of the time shown in the upper-left of the LCD keypad screen.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
o4-23: Date Format
No.
(Hex.)
Name Description
Default
(Range)
o4-23
(1550)
RUN
Date Format
Sets the date display format. This parameter is only available when using an LCD keypad.
2
(0 - 2)
Sets the date format that the drive uses for the fault history and other records.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
Note:
The Fault History in the Monitor Mode shows when faults occurred. Refer to Show Fault History on page 197 for more information.
o4-24: bAT Detection Selection
No.
(Hex.)
Name Description
Default
(Range)
o4-24
(310F)
RUN
bAT Detection Selection
Sets operation when the drive detects bAT [Keypad Battery Low Voltage] and TiM [Keypad Time Not
Set].
0
(0 - 2)
0 : Disable
The drive will not detect bAT or TiM.
1 : Enable (Alarm Detected)
TiM or bAT shows on the keypad, and operation continues. The output terminal set for Alarm [H2-01 to H2-03 = 10]
activates.
2 : Enable (Fault Detected)
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC activates, and MB-MC
deactivates.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents