Electrical Installation
3
3.5 Control Circuit Wiring
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 123
Figure 3.60 Locations of Switches
Table 3.15 I/O Terminals and Switches Functions
Position Switch Terminal Function Default
A DIP switch S2 -
Enables and disables the MEMOBUS/Modbus communications
termination resistor.
OFF
B Jumper Switch S5 FM, AM Sets terminals FM and AM to voltage or current output.
FM: V (voltage output)
AM: V (voltage output)
C
DIP switch S1-1 A1 Sets the input signal type (voltage/current). V (voltage input)
DIP switch S1-2 A2 Sets the input signal type (voltage/current). I (current input)
DIP switch S1-3 A3 Sets the input signal type (voltage/current). V (voltage input)
D DIP switch S4 A3 Sets MFAI or PTC input. AI (analog input)