EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Network Communications
6
6.3 MEMOBUS/Modbus Communications
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 331
Register No.
(Hex.)
Description
0022
Fault Contents
bit 0 1: During data writing, during motor switching
bit 1
Reserved
bit 2
bit 3 1: Upper/Lower Limit Fault
bit 4 1: Data Integrity Fault
bit 5 1: During EEPROM writing
bit 6
0: EEPROM writing
1: Change data only on the RAM
Note:
Enabled when H5-17 = 1 [ENTER Command Response @CPU BUSY = Write to RAM Only].
bit 7 - F
Reserved
0023
U1-01 [Frequency Reference]
Note:
o1-03 [Frequency Display Unit Selection] sets the units.
0024
U1-02 [Output Frequency]
Note:
o1-03 [Frequency Display Unit Selection] sets the units.
0025
U1-06 [Output Voltage Ref] (units: 0.1 V)
Note:
Use H5-10 [Modbus Register 0025H Unit Sel] to change the setting unit.
0026
U1-03 [Output Current] (units: 0.1 A)
0027 U1-08 [Output Power]
0028 U1-09 [Torque Reference]
0029
Fault Description 2
bit 0 Reserved
bit 1 GF [Ground Fault]
bit 2 PF [Input Phase Loss]
bit 3 LF [Output Phase Loss]
bit 4 rH [Braking Resistor Overheat]
bit 5 Reserved
bit 6 oH4 [Motor Overheat Fault (PTC Input)]
bit 7 - F Reserved