Troubleshooting
7
7.4 Fault
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 361
Code Name Causes Possible Solutions
CP2 Comparator 2 Limit Fault
The monitor value set in H2-26 [Comparator 2
Monitor Selection] was outside the range of H2-27
[Comparator 2 Lower Limit] and H2-28
[Comparator 2 Upper Limit].
Examine the monitor value and remove the cause of the fault.
Note:
The drive detects this error when the terminal is set to H2-01 to H2-03 = 67 [MFDO Function Selection = Comparator2].
Do a Fault Reset to clear the fault.
Set the stopping method for this fault in H2-35 [Comparator2 Protection Selection].
Code Name Causes Possible Solutions
CPF00 Control Circuit Error
A drive hardware problem occurred. Re-energize the drive.
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for these faults.
Code Name Causes Possible Solutions
CPF01 Control Circuit Error
A drive hardware problem occurred. Re-energize the drive.
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for these faults.
Code Name Causes Possible Solutions
CPF02 Control Circuit Error
A drive hardware problem occurred. Re-energize the drive.
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for these faults.
Code Name Causes Possible Solutions
CPF03 Control Circuit Error
A drive hardware problem occurred. Re-energize the drive.
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for these faults.
Code Name Causes Possible Solutions
CPF06
Control Circuit Error (EEPROM
memory Data Error)
The drive power supply was de-energized while a
communication option entered a parameter Write
command.
Set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire
Initialization, 3-Wire Initialization] and initialize the drive.
An EEPROM peripheral circuit error occurred. Re-energize the drive.
If the fault stays, replace the control board or the drive. For
information about how to replace the control board, contact
Yaskawa or your nearest sales representative.
Note:
The drive detects this error if there is an error in the data written to the drive EEPROM.
Do a Fault Reset to clear the fault.
Fault trace is not available for these faults.
Code Name Causes Possible Solutions
CPF07 Control Circuit Error
A drive hardware problem occurred. Re-energize the drive.
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for these faults.