7.5 Minor Faults/Alarms
394 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Code Name Causes Possible Solutions
External Fault [H1-04 = 2C to 2F] is set to MFDI
terminal S4, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EF5 External Fault (Terminal S5)
MFDI terminal S5 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S5.
External Fault [H1-05 = 2C to 2F] is set to MFDI
terminal S5, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EF6 External Fault (Terminal S6)
MFDI terminal S6 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S6.
External Fault [H1-06 = 2C to 2F] is set to MFDI
terminal S6, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EF7 External Fault (Terminal S7)
MFDI terminal S7 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S7.
External Fault [H1-07 = 2C to 2F] is set to MFDI
terminal S7, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EF8 External Fault (Terminal S8)
MFDI terminal S8 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S8.
External Fault [H1-08 = 2C to 2F] is set to MFDI
terminal S8, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EP24v External Power 24V Supply
The voltage of the main circuit power supply
decreased, and the 24 V power supply is supplying
power to the drive.
• Examine the main circuit power supply.
• Turn ON the main circuit power supply to run the drive.
Note:
• Set o2-26 [Ext. Power 24V Supply Display] to enable or disable EP24v detection.
• The drive will not output an alarm signal for this alarm.
Code Name Causes Possible Solutions
FAn Internal Fan Fault
The circulation fan stopped operating correctly. • Examine circulation fan operation.
• Re-energize the drive.
• Examine U4-03 [Cooling Fan Ope Time] and U4-04 [Cool Fan
Maintenance]. If there is damage to the circulation fan or if the
performance life of the fan is expired, replace the fan.
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code Name Causes Possible Solutions
FbH Excessive PID Feedback
The FbH detection level is set incorrectly. Adjust b5-36 [PID High Feedback Detection Lvl] and b5-37 [PID
High Feedback Detection Time].
There is a problem with the PID feedback wiring. Correct errors with the PID control wiring.