Troubleshooting
7
7.5 Minor Faults/Alarms
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 397
Code Name Causes Possible Solutions
The motor has overheated. Check the load level, acceleration/deceleration time, and motor
start/stop frequency (cycle time).
Decrease the load.
Increase the values set in C1-01 to C1-08 [Acceleration/
Deceleration Times].
Set E2-01 [Motor Rated Current (FLA)] correctly to the value
specified by the motor nameplate.
Make sure that the motor cooling system is operating correctly,
and repair or replace it if it is damaged.
Adjust E1-04 to E1-10 [V/f Pattern Parameters]. For motor 2,
adjust E3-04 to E3-10. Decrease the values set in E1-08 [Mid
Point A Voltage] and E1-10 [Minimum Output Voltage].
Note:
If the values set in E1-08 and E1-10 are too low, the overload
tolerance will decrease at low speeds.
Note:
When H3-02, H3-10, or H3-06 = E [MFAI Function Selection = Motor Temperature (PTC Input)], the drive detects this fault if the motor overheat signal entered to an analog
input terminal A1, A2, or A3 is more than the alarm detection level.
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will activate.
If the drive detects this error, it will operate the motor as specified by the stopping method set in L1-03 [Motor Thermistor oH Alarm Select].
Code Name Causes Possible Solutions
oL3 Overtorque 1
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load. Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque
Detection Time 1] settings.
Note:
The drive detects this fault if the drive output current is more than the level set in L6-02 for longer than L6-03.
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Set the conditions that trigger the minor fault using L6-01 [Torque Detection Selection 1].
Code Name Causes Possible Solutions
oL4 Overtorque 2
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load. Adjust L6-05 [Torque Detection Level 2] and L6-06 [Torque
Detection Time 2] settings.
Note:
The drive detects this error if the drive output current is more than the level set in L6-05 for longer than L6-06.
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Set the conditions that trigger the minor fault using L6-04 [Torque Detection Selection 2].
Code Name Causes Possible Solutions
oL5 Mechanical Weakening Detection 1
The drive detected overtorque as specified by the
conditions for mechanical weakening detection set in
L6-08 [Mechanical Fatigue Detect Select].
Do a deterioration diagnostic test on the machine side.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
If the drive detects this minor fault, it will operate the motor as specified by the Stopping Method set in L6-08.
Code Name Causes Possible Solutions
oS Overspeed
There is overshoot. Decrease C5-01 [ASR Proportional Gain 1] and increase C5-02
[ASR Integral Time 1].
Use H6-02 to H6-05 [Pulse Train Input Setting Parameters] to
adjust the pulse train gain.
There is an incorrect number of PG pulses set in the
drive.
Set H6-02 [Terminal RP Frequency Scaling] to the pulse train
frequency during 100% reference (maximum motor rotation speed).
The oS detection level is set incorrectly. Adjust F1-08 [Overspeed Detection Level] and F1-09 [Overspeed
Detection Delay Time].
Note:
The drive detects this error if the motor speed is more than the value set in F1-08 for longer than F1-09.
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will activate.
If the drive detects this error, it will operate the motor as specified by the stopping method set in F1-03 [Overspeed Detection Selection].