EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.6 Drive Specifications
494 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Item Specification
Overvoltage
Protection
200 V Class: Stops when the DC bus voltage is more than approximately 410 V
400 V Class: Stops when the DC bus voltage is more than approximately 820 V
Undervoltage
Protection
200 V Class: Stops when the DC bus voltage decreases to less than approximately 190 V
400 V Class: Stops when the DC bus voltage decreases to less than approximately 380 V
Momentary Power
Loss Ride-thru
Stops when power loss is longer than 15 ms.
Continues operation if power loss is shorter than 2 s (depending on parameter settings).
Note:
Stop time may be shortened depending on the load and motor speed.
Drive capacity will change the continuous operation time. A Momentary Power Loss Recovery Unit is necessary to continue operation through a 2 s
power loss on models 2004 to 2056 and 4002 to 4031.
Heatsink Overheat
Protection
The drive stops when the thermistor detects an IGBT temperature more than approximately 100 °C (212 °F). The trip temperature level is different for different
drive models.
Braking Resistor
Overheat Protection
Overheat detection for braking resistor (optional ERF-type, 3% ED)
Stall Prevention
Stall prevention is available during acceleration, deceleration, and during run.
Ground Fault
Protection
Electronic circuit protection
Note:
This protection detects ground faults during run. The drive will not provide protection when:
There is a low-resistance ground fault for the motor cable or terminal block
Energizing the drive when there is a ground fault.
DC Bus Charge LED
Charge LED illuminates when DC bus voltage is more than 50 V.
Braking Transistor
Models 2004 to 2138 and 4002 to 4168 have a braking transistor.
DC Link Choke
Models 2110 to 2415 and 4060 to 4720 have a DC link choke.
Table 10.13 Environment
Item
Specification
Area of Use
Indoors
Power Supply
Overvoltage Category III
Permitted frequency fluctuation: ±5%
Permitted voltage fluctuation: -15% to +10%
200 V Class:
Three-phase AC power supply 200 V to 240 V at 50/60 Hz 
DC power supply 270 V to 340 V
400 V Class:
Three-phase AC power supply 380 V to 480 V at 50/60 Hz
DC power supply 513 V to 679 V
6-Phase/12-Pulse 400 V Class:
Three-phase AC power supply 380 V to 480 V at 50/60 Hz
Ambient Temperature
Setting
IP00/UL Open Type: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Open Type/Heatsink External Mounting: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
IP55/UL Type 12 Heatsink External Mounting; front side: -10 °C to +50 °C (14 °F to 122 °F)
IP55/UL Type 12 Heatsink External Mounting; back side: -10 °C to +40 °C (14 °F to 104 °F)
When you install the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
Do not let the drive freeze.
You can use IP00/IP20/UL Open Type drives at a maximum of 60 °C (140 °F) when you derate the output current.
You can use IP20/UL Type 1 drives at a maximum of 50 °C (122 °F) when you derate the output current.
Humidity
95% RH or less
Do not let condensation form on the drive.
Storage Temperature
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Surrounding Area
Pollution degree 2 or less
Install the drive in an area without:
Oil mist, corrosive or flammable gas, or dust
Metal powder, oil, water, or other unwanted materials
Radioactive materials or flammable materials, including wood
Harmful gas or fluids
Salt
Direct sunlight

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals