11.17 U: Monitors
654 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
No.
(Hex.)
Name Description MFAO Signal Level
U4-16
(07D8)
Motor oL1 Level
Shows the integrated value of oL1 [Motor Overload] as a percentage of oL1 detection level.
Unit: 0.1%
10 V: 100%
U4-18
(07DA)
Reference Source
Shows the selected frequency reference source.
The keypad shows the frequency reference source as XY-nn as specified by these rules:
X: External Reference 1/2 Selection [H1-xx = 2] selection status
1: b1-01 [Frequency Reference Selection 1]
2: b1-15 [Frequency Reference Selection 2]
Y-nn: Frequency reference source
0-01: Keypad (d1-01 [Reference 1])
1-00: Analog input (unassigned)
1-01: MFAI terminal A1
1-02: MFAI terminal A2
1-03: MFAI terminal A3
2-02 to 2-17: Multi-step speed reference (d1-02 to d1-17 [Reference 2 to 16, Jog Reference])
3-01: MEMOBUS/Modbus communications
4-01: Communication option card
5-01: Pulse train input
7-01: DriveWorksEZ
9-01: Up/Down command
No signal output available
U4-19
(07DB)
Modbus FreqRef (dec)
Shows the frequency reference sent to the drive from the MEMOBUS/Modbus communications as a
decimal.
Unit: 0.01%
10 V: Maximum frequency
(0 V to +10 V)
U4-20
(07DC)
Option Freq Ref(dec)
Shows the frequency reference sent to the drive from the communication option as a decimal.
Unit: 0.01 %
10 V: Maximum frequency
(0 V to +10 V)
U4-21
(07DD)
Run Command Source
Shows the selected Run command source.
The keypad shows the Run command source as XY-nn as specified by these rules:
X: External Reference 1/2 Selection [H1-xx = 2] selection status
1: b1-02 [Run Command Selection 1]
2: b1-16 [Run Command Selection 2]
Y: Run command source
0: Keypad
1: Control circuit terminal
3: MEMOBUS/Modbus communications
4: Communication option card
7: DriveWorksEZ
nn: Run command limit status data
00: No limit status.
01: The Run command was left ON when the drive stopped in the Programming Mode.
02: The Run command was left ON when switching from LOCAL Mode to REMOTE Mode.
03: The Run command is in standby after the drive was energized until the soft charge bypass
contactor turns ON.
Note:
The drive will detect Uv1 [DC Bus Undervoltage] or Uv [Undervoltage] if the soft charge
bypass contactor does not turn ON after 10 s.
04: Restart after run stop is prohibited.
05: Fast stop has been executed using the MFDI terminal. Or, the motor has ramped to stop by
pressing the STOP key on the keypad.
06: b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] is set.
07: During baseblock while coast to stop with timer.
08: Frequency reference is below E1-09 [Minimum Output Frequency] during baseblock.
09: Waiting for the Enter command from PLC.
No signal output The keypad
shows the Run command
source as "XY-nn" as
specified by these rules:
available
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV