Parameter Details
12
12.3 b: Application
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 753
When the feedback signal is less than the level set in b5-13 for the time set in b5-14, the drive detects FbL.
When the feedback signal is less than the level set in b5-36 for the time set in b5-37, the drive detects FbH.
3 : Digital Out Only, @ PID Enable
The MFDO terminal set for PID Feedback Low or PID Feedback High activates. The keypad will not show a minor
fault/alarm. The drive continues operation.
When the MFDI terminal set to PID Disable [H1-xx = 19] activates, the drive disables fault detection.
4 : Alarm + Digital Out, @PID Enable
The drive detects FbL and FbH. The MFDO terminal set for PID Feedback Low or PID Feedback High activates. The
output terminal set for Alarm [H2-01 to H2-03 = 10] activates and the drive continues operation.
When the MFDI terminal set to PID Disable [H1-xx = 19] activates, the drive disables fault detection.
5 : Fault + Digital Out, @PID Enable
The drive detects FbL and FbH. Fault relay output terminal MA-MC activates, MB-MC turns OFF, and the drive
coasts to stop.
When the MFDI terminal set to PID Disable [H1-xx = 19] activates, the drive disables fault detection.
b5-13: PID Feedback Loss Detection Lvl
No.
(Hex.)
Name Description
Default
(Range)
b5-13
(01B1)
PID Feedback Loss
Detection Lvl
Sets the level that triggers PID Feedback Loss [FbL] detection as a percentage of the Maximum
Output Frequency.
0%
(0 - 100%)
The drive detects PID Feedback Loss [FbL] when the feedback signal decreases to less than the level set in b5-13 for
longer than the time set in b5-14 [PID Feedback Loss Detection Time].
b5-14: PID Feedback Loss Detection Time
No.
(Hex.)
Name Description
Default
(Range)
b5-14
(01B2)
PID Feedback Loss
Detection Time
Sets the length of time that PID Feedback must be less than b5-13 [PID Feedback Loss Detection
Lvl] to detect PID Feedback Loss [FbL].
1.0 s
(0.0 - 25.5 s)
b5-15: PID Sleep Function Start Level
No.
(Hex.)
Name Description
Default
(Range)
b5-15
(01B3)
PID Sleep Function Start
Level
Sets the output level that triggers the PID Sleep function.
Determined by A1-02
(0.0 - 590.0)
The drive goes into Sleep mode when the PID output or frequency reference is less than b5-15 for longer than the
time set to b5-16 [PID Sleep Delay Time]. The drive continues operation when the PID output or frequency reference
is more than b5-15 for longer than the time set to b5-16.
b5-16: PID Sleep Delay Time
No.
(Hex.)
Name Description
Default
(Range)
b5-16
(01B4)
PID Sleep Delay Time
Sets a delay time to start or stop the PID Sleep function.
0.0 s
(0.0 - 25.5 s)
b5-17: PID Accel/Decel Time
No.
(Hex.)
Name Description
Default
(Range)
b5-17
(01B5)
RUN
PID Accel/Decel Time
Raises or lowers the PID setpoint using the acceleration and deceleration times set to the drive. This
is a soft-starter for the PID setpoint.
0.0 s
(0.0 - 6000.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals