EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.3 b: Application
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 765
b8-19: E-Save Search Frequency
No.
(Hex.)
Name Description
Default
(Range)
b8-19
(0B40)
Expert
E-Save Search Frequency
Sets the frequency of Energy-saving control search operations. Usually it is not necessary to change
this setting.
Determined by A1-02
(10 - 300 Hz)
Note:
If low inertia causes vibration in the machine, increase the setting value in 10 Hz increments and check the response. If A1-02 = 8 [Control
Method Selection = EZOLV], increase the setting value in 1 Hz increments.
To make the motor more efficient, decrease the setting value in 1 Hz increments until the point immediately before machine vibration starts
to occur.
b8-20: E-Save Search Width
No.
(Hex.)
Name Description
Default
(Range)
b8-20
(0B41)
Expert
E-Save Search Width
Sets the amplitude of Energy-saving control search operations.
1.0 degrees
(0.1 - 5.0 degrees)
An increase in the value can make the operational efficiency better. However, if the load inertia is small, it may be
necessary to adjust the value to prevent machine vibration.
Note:
If low inertia causes vibration in the machine, decrease the setting value in 1.0-degree increments and check the response.
To make the motor more efficient, increase the setting value in 1.0-degreee increments until the point immediately before machine vibration
starts to occur.
b8-21: PM E-Save Search Gain
No.
(Hex.)
Name Description
Default
(Range)
b8-21
(0B42)
Expert
PM E-Save Search Gain
Sets the gain of Energy-saving control search operations.
0.3Hz
(0.1 - 20.0 Hz)
When you decrease the value of C5-01 [ASR Proportional Gain 1], also decrease the value of b8-21 to keep the
correct ratio.
b8-22: PM E-Save Search LPF Cutoff Freq
No.
(Hex.)
Name Description
Default
(Range)
b8-22
(0B43)
Expert
PM E-Save Search LPF
Cutoff Freq
Sets the frequency of the filter used to extract the high-efficiency phase from search operations.
Usually it is not necessary to change this setting.
10.0 Hz
(1.0 - 30.0 Hz)
b8-23: PM E-Save Search Limit
No.
(Hex.)
Name Description
Default
(Range)
b8-23
(0B44)
Expert
PM E-Save Search Limit
Sets the search operations output limit. Usually it is not necessary to change this setting.
15.0 degrees
(0.0 - 30.0 degrees)
When the motor characteristics are correct, increase this value to make the motor more efficient.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents