EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.5 d: References
806 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Figure 12.65 Up/Down 2 Example with Reference from Keypad and d4-01 = 1
Up/Down 2 Command with Frequency Reference from Input Sources Other Than the Keypad
When a Run command is active and you release the Up/Down 2 command for longer than 5 s, the drive will save
the bias value in d4-06 [Frequency Ref Bias (Up/Down 2)]. The drive saves the frequency reference + d4-06 as a
frequency reference value. The drive will use the new value as the frequency reference when it restarts.
Figure 12.66 Up/Down 2 Example with Other Reference than Keypad and d4-01 = 1
Note:
To use the combination of the frequency reference hold function and the Up/Down 2 function, configure the Up/Down 2 upper limit [d4-08]
and lower limit [d4-09] correctly.
Remove the Saved Frequency Reference Value
The procedure to remove the saved frequency reference value is different for different functions. Use these methods
to remove the value:
Release the input programmed for Accel/Decel Ramp Hold [H1-xx = A].
Set an Up or Down command while no Run command is active.
Use the Up/Down 2 Command to set d4-06 = 0.0 or set d4-06 = 0.0 during stop.
d4-03: Up/Down 2 Bias Step Frequency
No.
(Hex.)
Name Description
Default
(Range)
d4-03
(02AA)
RUN
Up/Down 2 Bias Step
Frequency
Sets the bias that the Up/Down 2 function adds to or subtracts from the frequency reference.
0.00 Hz
(0.00 - 99.99 Hz)
The operation is different for different setting values:
Setting d4-03 = 0.00 Hz
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals