12.7 F: Options
866 YASKAWA SIEPC71061737D GA800 Drive Technical Reference
0 : Disabled
1 : Enabled
F6-07: Multi-Step Ref @ NetRef/ComRef
No.
(Hex.)
Name Description
Default
(Range)
F6-07
(03A8)
Multi-Step Ref @ NetRef/
ComRef
Sets the function that enables and disables the multi-step speed reference when the frequency
reference source is NetRef or ComRef (communication option card or MEMOBUS/Modbus
communications).
0
(0, 1)
0 : Disable Multi-Step References
When NetRef or ComRef are the frequency reference source, the multi-step speed reference (2-step speed to 16-step
speed references) and the Jog Frequency Reference (JOG command) are disabled.
1 : Enable Multi-Step References
When NetRef or ComRef are the frequency reference source, the multi-step speed reference (2-step speed through 16-
step speed references) and the Jog Frequency Reference (JOG command) are enabled, and you can change the
frequency reference.
F6-08: Comm Parameter Reset @Initialize
No.
(Hex.)
Name Description
Default
(Range)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize F6-xx and F7-xx parameters when the drive is initialized with A1-03
[Initialize Parameters].
0
(0, 1)
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
Note:
When you use A1-03 to initialize the drive, this setting will not change.
F6-10: CC-Link Node Address
No.
(Hex.)
Name Description
Default
(Range)
F6-10
(03B6)
CC-Link Node Address
Sets the node address for CC-Link communication. Restart the drive after you change the parameter
setting.
0
(0 - 64)
Note:
Be sure to set a node address that is different than all other node addresses. Do not set this parameter to 0. Incorrect parameter settings will
cause AEr [Station Address Setting Error] errors and the L.ERR LED on the option will come on.
When the only drive is connected, you can connect a maximum of 42 nodes. Follow these rules to connect devices
that are not drives:
{(1 × a) + (2 × b) + (3 × c) + (4 × d)} 64
(a: number of units that occupies 1 node, b: number of units that occupies 2 nodes, c: number of units that occupies
3 nodes, d: number of units that occupies 4 nodes)
{(16 × A) + (54 × B) + (88 × C)} 2304
(A: number of remote I/O nodes (64 max.), B: number of remote device nodes (42 max.), C: number of local nodes
(26 max.))
F6-11: CC-Link Communication Speed
No.
(Hex.)
Name Description
Default
(Range)
F6-11
(03B7)
CC-Link Communication
Speed
Sets the communication speed for CC-Link communication. Restart the drive after you change the
parameter setting.
0
(0 - 4)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals