EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.7 F: Options
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 869
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-
MC turns OFF.
1 : Coast to Stop
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows E5, and the drive continues to operate.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set for Alarm [H2-01 to H2-03 = 10] activates.
F6-26: MECHATROLINK Allowable No of Err
No.
(Hex.)
Name Description
Default
(Range)
F6-26
(03CA)
MECHATROLINK
Allowable No of Err
Sets the number of times that the option must detect a bUS alarm to cause a bUS [Option
Communication Error].
2
(2 - 10 times)
F6-30: PROFIBUS-DP Node Address
No.
(Hex.)
Name Description
Default
(Range)
F6-30
(03CB)
PROFIBUS-DP Node
Address
Sets the node address for PROFIBUS-DP communication. Restart the drive after you change the
parameter setting.
0
(0 - 125)
Note:
Be sure to set a node address that is different than all other node addresses.
Node addresses 0, 1, and 2 are usually reserved for control, maintenance, and device self-diagnosis.
F6-31: PROFIBUS-DP Clear Mode Selection
No.
(Hex.)
Name Description
Default
(Range)
F6-31
(03CC)
PROFIBUS-DP Clear Mode
Selection
Sets what the drive will do after it receives the Clear Mode command.
0
(0, 1)
0 : Reset
Resets drive settings, for example frequency reference and I/O settings.
1 : Hold Previous State
The drive keeps the same status as before it received the command.
F6-32: PROFIBUS-DP Data Format Select
No.
(Hex.)
Name Description
Default
(Range)
F6-32
(03CD)
PROFIBUS-DP Data Format
Select
Sets the data format of PROFIBUS-DP communication. Restart the drive after you change the
parameter setting.
0
(0 - 5)
Note:
The H5-11 [Comm ENTER Command Mode] setting makes the RAM enter command necessary or not necessary to write parameters over
network communication. When F6-32 = 0, 1, or 2, the H5-11 setting does not have an effect. The RAM enter command is always necessary
to write parameters.
0 : PPO Type
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals